Fused Selection Tables Up To 690 V; Contactor Short-Circuit Protection - Siemens SIRIUS Configuration Manual

Load feeders
Hide thumbs Also See for SIRIUS:
Table of Contents

Advertisement

Fused selection tables up to 690 V

5.1

Contactor short-circuit protection

Short-circuit protection up to 100 kA
Type of coordination 1 and 2
Table 5- 1
Contactor
MLFB
Size S00
3RT2015-1..
3RT2016-1..
3RT2017-1..
3RT2018-1..
Size S0
3RT2024-1..
3RT2025-1..
3RT2026-1..
3RT2027-1..
3RT2028-1..
Please take account of the operating voltage
1)
Assignment and short-circuit protective devices acc. to DIN EN 60947-4-1
2)
Configuring SIRIUS Innovations
Configuration Manual, 04/2010, A8E56203880102-02
Fuse links according to IEC 60947 operating class gG,
(NH DIAZED, NEOZED; type 3NA, 5SB, 5SE)
P [kW]
3
4
5,5
7,5
5,5
7,5
11
15
18,5
Fuse links
1)
Type of coordination 1
2)
35
35
35
50
63
63
100
125
125
5
Type of coordination 2
2)
20
20
20
25
25
25
35
50
50
71

Advertisement

Table of Contents
loading

Table of Contents