Siemens SIRIUS Configuration Manual page 65

Load feeders
Hide thumbs Also See for SIRIUS:
Table of Contents

Advertisement

Standard
Setting
three-phase
range
motor
Overload
4-pole at
release
400 V AC
1)
Motor
Stan-
Motor
starter
dard
current
protector
output
I
P
kW
A
Short-circuit breaking capacity I
11
17,60
30,0 ... 36
CLASS 30
0,12
0,32
0,9 ... 1,25 3RV2011-0KA10
0,18
0,48
1,1 ... 1,6
0,25
0,68
1,4 ... 2
0,37
0,88
1,8 ... 2,5
0,55
1,20
2,8 ... 4
0,75
1,50
3,5 ... 5
1,1
2,20
4,5 ... 6,3
1,5
2,90
7,0 ... 10
2,2
3,90
9,0 ... 12,5 3RV2011-1KA10
3
5,20
11,0 ... 16
4
6,80
14,0 ... 20
5,5
9,20
20,0 ... 25
7,5
12,40
27,0 ... 32
Short-circuit breaking capacity I
7,5
12,40
30,0 ... 36
Order numbers for basic versions with screw terminals and spring-loaded terminals also possible. 3RA2921-1BA00 link
module can only be used with screw terminals.
Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data
1)
of the protected motor.
Rated control supply voltage 230 V AC, 50 Hz, other control voltages possible.
2)
The motor starter protector is to be set to maximum current value.
3)
Configuring SIRIUS Innovations
Configuration Manual, 04/2010, A8E56203880102-02
4.4 Motor starter protector + contactor + 3RB22, 3RB23 solid-state overload relay, or 3UF7
Motor starter
Contactor
protector
Starter
protection
3)
Order No.
Order No.
= 36 kA
q
3RV2021-4PA10
3RT1035-1AP00
3RT2015-1AP01
3RV2011-1AA10
3RT2015-1AP01
3RV2011-1BA10
3RT2015-1AP01
3RV2011-1CA10
3RT2015-1AP01
3RV2011-1EA10
3RT2024-1AP00
3RV2011-1FA10
3RT2024-1AP00
3RV2011-1GA10
3RT2024-1AP00
3RV2011-1JA10
3RT2026-1AP00
3RT2026-1AP00
3RV2021-4AA10
3RT2026-1AP00
3RV2021-4BA10
3RT2027-1AP00
3RV2021-4DA10
3RT2027-1AP00
3RV2021-4EA10
3RT2027-1AP00
= 36 kA
q
3RV2021-4PA10
3RT1035-1AP00
Size
Overload relay (solid-
2)
state)
Order No.
S0/S2
3UF7101-1AA00-0/
3RB2906-2DG1
S00/S00
3UF7100-1AA00-0/
3RB2906-2BG1
S00/S00
3UF7100-1AA00-0/
3RB2906-2BG1
S00/S00
3UF7100-1AA00-0/
3RB2906-2BG1
S00/S00
3UF7100-1AA00-0/
3RB2906-2BG1
S00/S0
3UF7100-1AA00-0/
3RB2906-2BG1
S00/S0
3UF7100-1AA00-0/
3RB2906-2BG1
S00/S0
3UF7100-1AA00-0/
3RB2906-2BG1
S00/S0
3UF7100-1AA00-0/
3RB2906-2BG1
S00/S0
3UF7101-1AA00-0/
3RB2906-2DG1
S0/S0
3UF7101-1AA00-0/
3RB2906-2DG1
S0/S0
3UF7101-1AA00-0/
3RB2906-2DG1
S0/S0
3UF7101-1AA00-0/
3RB2906-2DG1
S0/S0
3UF7101-1AA00-0/
3RB2906-2DG1
S0/S2
3UF7101-1AA00-0/
3RB2906-2DG1
Selection tables 500 V AC
Setting range
Overload
release
Overload relay
A
2,4 ... 25,00
0,3 ... 3,00
0,3 ... 3,00
0,3 ... 3,00
0,3 ... 3,00
0,3 ... 3,00
0,3 ... 3,00
0,3 ... 3,00
0,3 ... 3,00
2,4 ... 25,00
2,4 ... 25,00
2,4 ... 25,00
2,4 ... 25,00
2,4 ... 25,00
2,4 ... 25,00
65

Advertisement

Table of Contents
loading

Table of Contents