Motor Starter Protector + 3Rw40 Soft Starter - Siemens SIRIUS Configuration Manual

Load feeders
Hide thumbs Also See for SIRIUS:
Table of Contents

Advertisement

4.7

Motor starter protector + 3RW40 soft starter

CLASS 10, type of coordination 1,
short-circuit breaking capacity
Standard three-phase motor
4-pole at
400 V AC
1)
Standard
Motor current
output
I
P
kW
A
7,5
15,5
11
22
15
29
18,5
35
3)
Order numbers for basic versions with screw terminals and spring-loaded terminals also possible. 3RA2921-1BA00 link
module can only be used with screw terminals.
Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data
1)
of the protected motor.
Rated currents taken into account at 40 °C ambient temperature. Rated control supply voltage 230 V AC, 50 Hz, other
2)
control voltages possible.
Discrete mounting only, without a link module.
3)
Configuring SIRIUS Innovations
Configuration Manual, 04/2010, A8E56203880102-02
I
= 10 kA
q
Setting range
Motor starter protector
Overload release
Motor protection
Motor starter protector
A
Order No.
11 ... 16
3RV2011-4AA10
20 ... 25
3RV2021-4DA10
27 ... 32
3RV2021-4EA20
34 ... 40
3RV2021-4FA10
Selection tables 500 V AC
4.7 Motor starter protector + 3RW40 soft starter
Soft starter
2)
Order No.
3RW4024-1BB14
3RW4026-1BB14
3RW4027-1BB14
3RW4028-1BB14
Size
MSP / 3RW40
S0/S0
S0/S0
S0/S0
S0/S0
69