Siemens Sitrans Probe LU Instruction Manual
Hide thumbs Also See for Sitrans Probe LU:
Table of Contents

Advertisement

Quick Links

Oxley Creek WWTP Water Reclamation
(Probe LU Manual) Vendor Manual
Instruction Manual October 2005
sitrans
Doc Id: VM11
Active Date: 15/12/2006

Advertisement

Table of Contents
loading

Summary of Contents for Siemens Sitrans Probe LU

  • Page 1 Oxley Creek WWTP Water Reclamation Doc Id: VM11 (Probe LU Manual) Vendor Manual Active Date: 15/12/2006 Instruction Manual October 2005 sitrans...
  • Page 2 The user is responsible for all changes and repairs made to the device by the user or the user’s • agent. All new components are to be provided by Siemens Milltronics Process Instruments Inc. • Restrict repair to faulty components only.
  • Page 3: Table Of Contents

    SITRANS Probe LU (PROFIBUS PA) ................4 Applications ..........................5 Level, volume, or flow ........................ 5 SITRANS Probe LU System Implementation ................5 Programming ..........................6 SITRANS Probe LU (PROFIBUS PA) Approvals and Certificates ........6 Specifications ........................7 Installation ........................11 Mounting Location ..........................11 Mounting Instructions ........................12 SITRANS Probe LU Dimensions ....................13...
  • Page 4 Oxley Creek WWTP Water Reclamation Doc Id: VM11 (Probe LU Manual) Vendor Manual Active Date: 15/12/2006 Diagnosis reply (applies only to cyclic masters) ...............28 Acyclic Diagnostics ........................28 Acyclic Extended Diagnostics (General Fault Codes) ............30 Acyclic Data ............................32 Configuration Example ......................33 Accessing parameters remotely .....................33 Functions .............................33 Changing parameter settings ....................33...
  • Page 5 Oxley Creek WWTP Water Reclamation Doc Id: VM11 (Probe LU Manual) Vendor Manual Active Date: 15/12/2006 Appendix G: Asynchronous Communications Data M ap ........61 Directory............................61 Physical Block 1......................... 61 Analog Input Function Blocks: AIFB1 and AIFB2 .............. 64 Level Transducer Block......................66 Appendix H: Parameter Descriptions ................73 Identification ............................73 Configuration..........................
  • Page 6 Oxley Creek WWTP Water Reclamation Doc Id: VM11 (Probe LU Manual) Vendor Manual Active Date: 15/12/2006...
  • Page 7: Safety Notes

    • Connect the equipment to an outlet on a different circuit from the one to which the receiver is connected. • Consult an experienced radio/TV technician for help. This warning symbol is used when there is no corresponding caution symbol on the product. 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 1...
  • Page 8: The Manual

    SITRANS Probe LU (PROFIBUS PA). • This manual applies to the SITRANS Probe LU (PROFIBUS PA) only. This manual will help you set up your SITRANS Probe LU for optimum performance. We always welcome suggestions and comments about manual content, design, and accessibility.
  • Page 9 µs Polybutylene Terephthalate Polyether Imide Programmable Logic Controller PVDF Polyvinylidene fluoride parts per million measured value SELV Safety Extra Low Voltage equivalent value sensitivity threshold Input voltage Output voltage 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 3...
  • Page 10: Sitrans Probe Lu (Profibus Pa)

    The transducer is available in ETFE (ethylene-tetrafluoroethylene) or PVDF (polyvinylidene fluoride), allowing SITRANS Probe LU to be used in a wide variety of industries and applications using corrosive chemicals. The ultrasonic transducer contains a temperature-sensing element to compensate for temperature changes in the application.
  • Page 11: Applications

    (Probe LU Manual) Vendor Manual Active Date: 15/12/2006 Applications Level, volume, or flow SITRANS Probe LU is designed to measure levels of liquids in a variety of applications: • storage type vessels • simple process vessels with some surface agitation •...
  • Page 12: Programming

    (Probe LU Manual) Vendor Manual Active Date: 15/12/2006 Programming SITRANS Probe LU carries out its level measurement function according to the set of built-in parameters. Parameter changes can be made via the Siemens Milltronics infrared handheld programmer, or via a PC using SIMATIC PDM.
  • Page 13: Specifications

    (Probe LU Manual) Vendor Manual Active Date: 15/12/2006 Specifications Note: Siemens Milltronics makes every attempt to ensure the accuracy of these specifications but reserves the right to change them at any time. SITRANS Probe LU (PROFIBUS PA) Pow er • Bus powered On PROFIBUS PA, as per IEC 61158-2 •...
  • Page 14 Temperature dependent: typical value at +20 °C (+68 °F); maximum value at +80 °C (+176 °F) Submergence test under water at 2 m (6.5 ft) depth for 24 hours. Page 8 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 15 Class I, Div. 2, Groups A,B, C, D Intrinsically Safe wiring drawing (FM/CSA) on page 107 for drawing number 23650617. Non-incendive (FM Class I, Div. 2) wiring drawing on page 111 for drawing number 23650583. 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 9...
  • Page 16 Doc Id: VM11 (Probe LU Manual) Vendor Manual Active Date: 15/12/2006 Programmer (infrared keypad) Siemens Milltronics Infrared IS (Intrinsically Safe) handheld programmer: for all locations, including hazardous. • approval ATEX II 1 G EEx ia IIC T4, SIRA 01ATEX2147 FM/CSA: Class I, Div. 1, Groups A, B, C, D •...
  • Page 17: Installation

    • Installation shall only be performed by qualified personnel and in accordance w ith local governing regulations. • SITRANS Probe LU is to be used only in the manner outlined in this manual, otherw ise protection provided by the equipment may be impaired.
  • Page 18: Mounting Instructions

    M ounting Instructions Note: • Ideally, mount SITRANS Probe LU so that the face of the transducer is at least 300 mm (1 ft) above the highest anticipated level. SITRANS Probe LU is available in three thread types: •...
  • Page 19: Sitrans Probe Lu Dimensions

    51. 1 mm (2.01") 54.0 mm (2. 1 3") Flange Adaptor (optional) SITRANS Probe LU can be fitted with the optional 3" (80 mm) flange adaptor for mating to 3" ANSI, DIN 65PN10, and JIS 10K3B flanges. SITRANS Probe LU "A"...
  • Page 20: W Iring

    Strip the cable jacket for approximately 70 mm (2.75") from the end of the PROFIBUS PA cable, and thread the wires through the gland Safety Extra Low Voltage If cable is routed through conduit, use only approved suitable-size hubs for waterproof applications. Page 14 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 21 PROFIBUS PA User and Installation Guidelines work properly. Please refer to the (order number 2.092), available from www.profibus.com. The instrument shield connection is internally connected to the external ground lug. 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 15...
  • Page 22: Startup

    Analog Input Function Block 1/AIFB1). System status is displayed on the LCD, or on a remote communications terminal. Note: SITRANS Probe LU (PROFIBUS PA) continues to monitor in and out values even when the device is in PROGRAM mode. Startup Display (RUN mode)
  • Page 23: Programming Sitrans Probe Lu (Profibus Pa)

    PROGRAM mode, then enter the menu number (see menu structure on page 49). For more instructions on local programming using the handheld programmer, please Appendix D: programming via the handheld programmer on page 42. 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 17...
  • Page 24: Program Mode Display

    Active Date: 15/12/2006 PROGRAM M ode Display Note: SITRANS Probe LU (PROFIBUS PA) continues to monitor In and Out values even when the device is in PROGRAM mode. 1 – Primary region (displays parameter value) 2 – Menu number region (displays Menu number) 3 –...
  • Page 25: Quick Setup

    Note: Keep infrared devices such as laptops, cell phones, and PDAs, away from SITRANS Probe LU to prevent inadvertent operation. Power up the instrument. SITRANS Probe LU starts in mode, and the LCD displays the output of AIFB1. Setting the PROFIBUS address via the handheld programmer Notes: •...
  • Page 26: Performing Calibration Via Profibus Pa

    Probe LU product page of our website, at: https://pia.khe.siemens.com/index.asp?Nr=11157) Changing parameter settings • First launch SIMATIC PDM, connect to SITRANS Probe LU, and upload data from the device. • Adjust parameter values in the parameter view field (right side of screen).
  • Page 27: Using Auto False Echo Suppression

    SITRANS Probe LU is now ready to operate. Using Auto False Echo Suppression If SITRANS Probe LU displays a false high level, or the reading is fluctuating between the correct level and a false high level, you can use the Auto False Echo Suppression parameters to prevent false echo detection.
  • Page 28: Remote Operation Via Profibus Pa

    Active Date: 15/12/2006 Remote operation via PROFIBUS PA SITRANS Probe LU (PROFIBUS PA) is a Class B, Profile Version 3.0, rev. 1, PA device. It supports Class 1 Master for cyclic and acyclic data exchange, and Class 2 for acyclic services.
  • Page 29: Configuration

    In the case of the Probe LU (PROFIBUS PA), the maximum PROFIBUS current is user- PROFIBUS Current Consumption selectable, and can be either 12, 13, 15, or 20 mA. (See page 79.) 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 23...
  • Page 30: Cyclic Versus Acyclic Data

    Input information is always requested at every bus scan and is set up as cyclic data. Configuration information is only needed periodically and is set up as acyclic data. Cyclic Data When you configure SITRANS Probe LU on the PROFIBUS PA bus, there are two slots available for modules. Note: Each of the slots has to have a module defined in it.
  • Page 31: Status Byte

    This could happen when a firmware download has been done, but a system reset has not been done. This could also happen if the function blocks are not configured properly using the handheld programmer, PDM or acyclic services. 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 25...
  • Page 32: Condensed Status

    Usability of the process value depends on the applica- tion. 0x68 UNCERTAIN – main- Value is potentially invalid. Cause is a wear detected ...0x6B tenance demanded in the device. Maintenance is demanded within a short-term period. Page 26 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 33 No measurement available because of 0x25 nance invalid process conditions. 0x3C BAD – function check / local over- Occurs during cleaning or calibration ...0x3F ride, value not usable process. 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 27...
  • Page 34: Diagnostics

    0x02000000 Mechanical failure 0x04000000 Motor Temperature too high 0x08000000 Electronics temperature too high 0x10000000 Memory error 0X20000000 Measurement failure 0X40000000 Device not initialized (no calibration) 0x80000000 Self calibration failed Page 28 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 35 10 seconds. PNO – PROFIBUS User Organization Values of the DIAGNOSIS bit: = not set = set 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 29...
  • Page 36: Acyclic Extended Diagnostics (General Fault Codes)

    Point and Low Cali- Calibration Point and Low Cali- bration Point are the same. bration Point are different. Internal temperature sen- Repair required: contact your sor has failed. local Siemens representative. Page 30 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 37 1 master (PLC), PLC was parameterized. and re-parameterize with the new Ident number. Factory calibration for the Repair required: contact your internal temperature sen- local Siemens representative. sor has been lost. 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 31...
  • Page 38: Acyclic Data

    Acyclic Data SITRANS Probe LU supports up to four simultaneous connections by a Class 2 Master (C2 connection). It supports one connection by a Class 1 Master (C1 connection). A list of all acyclic data, including address (slot and index), format, range of values, start value,...
  • Page 39: Configuration Example

    To configure and use PROFIBUS PA w ith an S7-300/ 400 PLC If SITRANS Probe LU is not listed in the STEP 7 device catalog, you can download the GSD file from the product page of our web site at: https://pia.khe.siemens.com/index.asp?Nr=11157 under...
  • Page 40 Oxley Creek WWTP Water Reclamation Doc Id: VM11 (Probe LU Manual) Vendor Manual Active Date: 15/12/2006 Notes Page 34 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 41: Appendix A: Technical References

    The transducer emits a series of ultrasonic pulses: each pulse is reflected as an echo from the material and sensed by the transducer. The echo is processed by SITRANS Probe LU, using Siemens Milltronics’ proven Sonic Intelligence techniques. Filtering is applied to help discriminate between the true echo from the material and false echoes from acoustic and electrical noise, and agitator blades in motion.
  • Page 42: Loss Of Echo (Loe)

    (Probe LU Manual) Vendor Manual Active Date: 15/12/2006 • When Echo Lock is Off, SITRANS Probe LU responds immediately to a new measurement (within the restrictions set by the Maximum Fill / Empty Rate). However, measurement reliability is affected. •...
  • Page 43: Failsafe Value

    Auto False-Echo Suppression The TVT adjustment parameters allow you to set a TVT (Time Varying Threshold) curve, so that SITRANS Probe LU will ignore false echoes. The default TVT curve hovers above the echo profile, and effectively screens out small false echoes.
  • Page 44 Distance (meters) Turn on Auto False-Echo Suppression when the material level is substantially lower than process full level (ideally when the tank is empty or almost empty). Page 38 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 45: Open Channel Monitoring (Ocm)

    Open Channel M onitoring (OCM ) OCM converts a level reading (head) into a flow value using a linear algorithm. SITRANS Probe LU can convert a head level measurement into a flow rate, using an eleven breakpoint head-versus-flow characteristic curve. This chart is usually available from the manufacturer of the v-notch weir, Parshall flume, or other open channel device.
  • Page 46: Appendix B: Troubleshooting

    Write locking that Write Locking is Off (see on page 45). If you try to set a SITRANS Probe LU parameter via remote communications, but the parameter remains unchanged, make sure remote operation is enabled (see Remote operation enable on page 45). Also make sure that Write Locking is Off (see Write Locking on page 76).
  • Page 47: Appendix C: M Aintenance

    Please note the following: • The user is responsible for all changes and repairs made to the device. • All new components must be provided by Siemens Milltronics Process Instruments Inc. • Restrict repair to faulty components only. •...
  • Page 48: Appendix D: Programming Via The Handheld Programmer

    Appendix D: programming via the handheld programmer Although the complete range of parameters is only accessible via PDM , you can access and adjust many of the parameters via the Siemens Milltronics infrared handheld programmer. Appendix H: Parameter Descriptions •...
  • Page 49: Handheld Programmer: Key Functions In Run Mode

    Updates internal enclosure temperature value and displays it in LCD secondary region. Updates echo confidence value and displays it in LCD secondary region. Updates measurement value and displays it in LCD secondary region. 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 43...
  • Page 50: Handheld Programmer: Key Functions In Navigation Mode

    Change the sign of the entered value. Add the corresponding character. Security Local operation enable Local Operation can be enabled or disabled via PDM. Go to and select the desired setting. Page 44 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 51: Write Locking

    Config Menu, then scroll down to REMLOCK. 1. Identification 1.2. Configuration 1.2.2. Remote Lock • To enable programming, set REMLOCK to . To disable programming, enter 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 45...
  • Page 52: How To Do A Master Reset

    The value returns to the default factory setting. Manufacturer’s settings: AIFB Filter Time Constant = 10 s LTB values set for 0 - 20 m (Low and High Calibration points; Near Range and Far Range) Page 46 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 53: Fault Reset

    (default is 0). Go to and enter the corresponding value in percent (default is 100). SITRANS Probe LU is now ready to operate. 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 47...
  • Page 54 Oxley Creek WWTP Water Reclamation Doc Id: VM11 (Probe LU Manual) Vendor Manual Active Date: 15/12/2006 Notes Page 48 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 55: Appendix E: Lcd Menu Structure

    Oxley Creek WWTP Water Reclamation Doc Id: VM11 (Probe LU Manual) Vendor Manual Active Date: 15/12/2006 Appendix E: LCD menu structure SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 49 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 56 Maintenance settings on page 52. 1. PV settings 2. SV1 3. SV2 6. Condensed status Condensed Status Setup on page 53 Page 50 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 57 2. Lower Limit Warning 3. Upper Limit Warning 4. Upper Limit Alarm 5. Limit Hysteresis 6. Min. Out 7. Max Out 1. Failsafe Mode 2. Failsafe Value A. Decimal Point 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 51...
  • Page 58 3. Maintenance Demanded Limit 4. Maintenance Alert Activation 5. Total Calibration Interval 6. Units 7. Maintenance Status 8. Acknowledge Status 9. Acknowledge See Condensed Status Set- up page 53 Page 52 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 59 38. Tech Module Hardware S37 39. Tech Module Ramp S38 40. Transducer Temperature Sensor S39 41. Transducer Temperature High S40 42. Transducer Temperature Low S41 43. Transducer Temperature Calibration S42 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 53...
  • Page 60 Oxley Creek WWTP Water Reclamation Doc Id: VM11 (Probe LU Manual) Vendor Manual Active Date: 15/12/2006 Notes Page 54 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 61: Appendix F: Profibus Pa Profile Structure

    The Level Transducer Block carries out adjustments to the sensor, such as level calibration and volume calibration. It supplies the outputs used by either or both of the AIFBs. 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 55...
  • Page 62: Description Of The Blocks

    (Level Units) AIFB2 High Level Low Level (Analog Point Point Input) Secondary Value 2 [Distance 1] (Sensor Units) Sensor Level unit Secondary Value 2 conversion [Distance 2] (Level Units) Page 56 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 63 High Level Point Point Sensor Value Distance 1 or 2 (default: 100%) (SV2 or SV3) Level Low Level Point Calibration Level Offset Point (default: 0%) Secondary Value 1 Range 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 57...
  • Page 64: Analog Input Function Blocks 1 And 2

    The output from the Level Transducer Block can be called the Primary Value (PV) or Secondary Value (SV1, SV2, or SV3). When it becomes the input to the AIFB, it is called the Process Variable. Page 58 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 65 Variable scale are the same as the units used for the LTB output.) Output units together with Process Variable range determine how the LTB output is converted to whatever units the customer wants. 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 59...
  • Page 66 A hysteresis parameter prevents toggling in the Status field of the OUT value.) The OUT VALUE parameter is the value for the cyclic data transfer. Page 60 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 67: Appendix G: Asynchronous Communications Data M Ap

    Block Object DD Revision UNSIGNED_INTEGER(2) Profile INTEGER (2) Profile Revision INTEGER (2) Execution Time UNSIGNED_INTEGER (1) Number of Parameters UNSIGNED_INTEGER(2) Index of View 1 UNSIGNED_INTEGER(2) Number of views UNSIGNED_INTEGER(1) 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 61...
  • Page 68 UNSIGNED_INTEGER (1) Features Supported Value INTEGER (4) Features Enabled Value INTEGER (4) Condensed Status Value INTEGER (1) Mode Condensed Status Value Byte array (50) Setup Order Number ASCII (32) Page 62 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 69 Maintenance Demanded Calibration Interval UNSIGNED_INTEGER (4) Limit Maintenance Alarm INTEGER (1) Activation Total Calibration Interval UNSIGNED_INTEGER (4) Total Calibration Interval Calibration acknowledge INTEGER (1) Extended Diagnostics Value BIT_ENUMERATED (6) 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 63...
  • Page 70: Analog Input Function Blocks: Aifb1 And Aifb2

    UNSIGNED_INTEGER (2) Batch Informa- tion Batch Operation UNSIGNED_INTEGER(2) Batch Phase UNSIGNED_INTEGER(2) Output Value FLOAT (2) Quality UNSIGNED_INTEGER (1) Status UNSIGNED_INTEGER (1) Upper FLOAT (2) PV Range Lower FLOAT (2) Page 64 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 71 Quality INTEGER (1) Status INTEGER (1) Quality Simulation Value FLOAT (2) Simulation Enabled INTEGER (1) Out Unit Text ASCII(16) Max Out Value FLOAT (2) Min Out Value FLOAT (2) 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 65...
  • Page 72: Level Transducer Block

    INTEGER (1) PV Units (Level/ Value INTEGER (2) Volume) Measured Value Value FLOAT (2) (Level) Level Units Value UNSIGNED_INTEGER (2) Sensor Value Value FLOAT (2) Sensor Units Value INTEGER (2) Page 66 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 73 Value Process Temper- Value FLOAT (2) ature Temperature Value INTEGER (2) Units Max Process Value FLOAT (2) Temperature Min Process Value FLOAT (2) Temperature Temperature Value INTEGER (1) Source 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 67...
  • Page 74 INTEGER (1) Mode INTEGER (1) Auto TVT Range FLOAT (2) Reserved FLOAT (2) Reserved FLOAT (2) Long shots INTEGER (1) Number of shots Short shots INTEGER (1) Reserved INTEGER (1) Page 68 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 75 Meas x FLOAT (2) Step x TVT FLOAT (2) Echo Marker UNSIGNED_INTEGER Profile data part Value byte array Profile data part Value byte array Profile data part Value byte array 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 69...
  • Page 76 INTEGER (1) Point 15 INTEGER (1) Point 16 INTEGER (1) Point 17 INTEGER (1) Point 18 INTEGER (1) Point 19 INTEGER (1) Point 20 INTEGER (1) Point 21 INTEGER (1) Page 70 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 77 FLOAT (2) Temperatures Transducer Temperature FLOAT (2) Substance Value INTEGER (1) TVT Type Value INTEGER (1) Remaining Sensor Lifetime UNSIGNED_INTEGER (4) Sensor Life Status BIT_ENUMERATED (1) Maintenance ack BIT_ENUMERATED (1) 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 71...
  • Page 78 BIT_ENUMERATED (1) Maintenance Required Limit UNSIGNED_INTEGER (4) Calibration Maintenance Demanded Limit UNSIGNED_INTEGER (4) Interval Maintenance Alert Activation INTEGER (1) Total Service Interval UNSIGNED_INTEGER (4) Service Interval Service ack INTEGER (1) Page 72 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 79: Appendix H: Parameter Descriptions

    There is no specific recommended use. 1.2. Configuration 1.2.1. Device Address (default 126) The unique address of the device on the network (also called PROFIBUS address). Values Open the menu 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 73...
  • Page 80: Device

    Determines the length of time (in seconds) the device will stay in PROGRAM mode without any key presses occurring. 1.3. Device Manufacturer References a specific manufacturer, usually the name of the company responsible for the manufacture of this Field Device. Page 74 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 81 Enables/disables programming the device via the handheld programmer.When disabled, the user still has access to the mode control of the two Analog Input Function Blocks. Go to and select the desired setting. 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 75...
  • Page 82: Statistics

    The number of power cycles that have occurred since manufacture. Open menu 1.4.3. Internal Temperature The internal electronics temperature. Value (view only) Degrees C Open menu , and select the tab Page 76 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 83: Input

    Out of Service (O/S) Hand programmer Manual Mode (MAN) values Automatic Mode (AUTO) 2.2. Reset Filter Resets the rate filter. Hand the sensor value immediately goes to the target programmer distance value 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 77...
  • Page 84: Standard Setup

    Slower settings provide higher accuracy: faster settings allow for more level fluctuation. 2.3.2. Echo Lock Note: Ensure the agitator is always running while SITRANS Probe LU is monitoring the vessel, to avoid stationary blade detection. Selects the measurement verification process. Hand programmer...
  • Page 85 This parameter cannot be reset to factory default settings. Temperature dependent: typical values at +20 °C (+68 °F); maximum values at +80 ° C (+176 °F). 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 79...
  • Page 86: Sensor Calibration

    Sensor Value: the value produced by the echo processing, which represents the dis- tance from the Sensor Reference Point to the target. Level Value: the level measured in level units. Page 80 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 87 , and click on the button for Wet or Dry calibration. Enter the values for Low Calibration Point, Low Calibration Level, High Calibration Point, High Level Point, then click on 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 81...
  • Page 88: Measuring Limits

    The minimum recorded Sensor value, defined in Sensor units. Open menu , and click Sensor tab. 2.5.2. Max. Measured Value The maximum recorded Sensor value, defined in Sensor units. Open menu , and click Sensor tab Page 82 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 89: Linearization

    Defines the tank shape and allows the Probe LU to calculate volume instead of level. If is selected, no volume conversion is performed. Select the tank shape matching the monitored tank or reservoir (see table on next page). 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 83...
  • Page 90 (flat linearization volume bottom) conical or pyramidal linearization volume, bottom dimension A linearization volume, parabolic bottom dimension A linearization volume, half-sphere bottom dimension A Page 84 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 91 Hand programmer values Range: in units (P005 Related Parameters Tank Shape Go to and select desired level units. Key in the height of the vessel bottom in level units. 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 85...
  • Page 92: Detailed Setup

    Enter up to 32 level breakpoints, where the corresponding volume is known. The values corresponding to 100% and 0% levels must be entered. The breakpoints can be ordered from top to bottom, or the reverse. Breakpoints are normalized to 0. Page 86 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 93 Use the level breakpoints to enter head level values, and the volume breakpoints to enter flow volumes. Each segment defined by a head breakpoint requires a corresponding flow value, so that SITRANS Probe LU can make the head-to-flow calculations. Use the Flow table associated with your open channel device (Parshall flume, v-notch weir, or other measuring device) to calculate the flow rate for each breakpoint.
  • Page 94 Repeat steps and , until values have been entered for all the required breakpoints. Break- Head Flow point (level) (volume) 0.4 m 113.5 0.3 m 55.3 0.2 m 20.07 Note: Illustrated breakpoint values are for example purposes only. Page 88 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 95 SMPI service personnel) 2.7.3.2. Threshold Short (default 10) Note: The Threshold parameters are for use by authorized Siemens Milltronics Service personnel or technicians familiar with Siemens Milltronics echo processing techniques. Sets the minimum Short Shot echo confidence that the echo must meet in order to be considered a valid echo.
  • Page 96 Once echo is outside the window, a specified number of consecutive echoes must appear above the echo locked onto, before measurement is accepted as valid. This parameter is for use only by Siemens Milltronics service technicians. Page 90 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL...
  • Page 97 Maximum distance from the reference point , within which an echo should be considered valid. Hand programmer values Range: to This parameter is for use only by Siemens Milltronics service technicians. The transducer face. 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 91...
  • Page 98 Open the menu 2.7.6.3. Echo Strength Displays the amplitude (in dB above 1 µV rms) of the echo selected as the measurement echo. Values (view only) Open the menu Page 92 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 99 (Probe LU Manual) Vendor Manual Active Date: 15/12/2006 2.7.7. TVT setup First SITRANS Probe LU learns the echo profile. Then the learned profile, or part of the learned profile, is used to screen out false echoes. 2.7.7.1. TVT Hover Level...
  • Page 100 Distance (meters) 2.7.7.9. Shaper Mode (default Off) Turns TVT Shaper on or off. (For use only by Siemens Milltronics personnel.) This parameter cannot be reset to the factory default. Page 94 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL...
  • Page 101 Adjusts the Probe LU response to decreases in the actual material level. Empty Rate is automatically updated whenever Response Rate is altered. Values Range: m/min. Altered by Response Rate Related Units (Level) High Level Point 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 95...
  • Page 102: Output

    Used to request an operating mode from the Function Block. (Out-of-service mode is a safety feature, used for service purposes to stop the transducer firing). Out of Service (O/S) Values Manual Mode (MAN) Automatic Mode (AUTO) Page 96 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 103 Identifies the active Control Recipe Unit Procedure or the related Unit (for example, reactor, centrifuge, drier). 3.1.5.3. Batch operation (default 0) Identifies the active Control Recipe Operation. 3.1.5.4. Batch Phase (default 0) Identifies the active Control Recipe Phase. 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 97...
  • Page 104 The setting for the lower warning limit in engineering units. 3.1.8.3. Upper Limit Warning The setting for the upper warning limit in engineering units. 3.1.8.4. Upper Limit Alarm The setting for the upper alarm limit in engineering units Page 98 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 105: Aifb2

    If the code list does not contain a desired unit for the OUT parameter, (see General Requirement) you can write the specific text in this parameter. 3.2. AIFB2 (See AIFB1: the parameters for AIFB2 are identical.) 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 99...
  • Page 106: Certificates And Approvals

    5.3.1. Time Elapsed Since Last Service 5.3.2. Maintenance Required Limit 5.3.3. Maintenance Demanded Limit 5.3.4. Maintenance Alert Activation 5.3.5. Total Service Interval 5.3.6. Units 5.3.7. Maintenance Status 5.3.8. Acknowledge Status 5.3.9. Acknowledge Page 100 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 107: Calibration Interval

    6.1.31. Memory EEPROM Flags S30 (Status; Diagnosis) 6.1.32. Memory Flash S31 (Status; Diagnosis) 6.1.33. Ident Violation S32 (Status; Diagnosis) 6.1.34. Internal Temperature Calibration S33 (Status; Diagnosis) (continued on next page) 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 101...
  • Page 108 6.1.39. Tech Module Ramp S38 (Status; Diagnosis) 6.1.40. Transducer Temperature Sensor S39 (Status; Diagnosis) 6.1.41. Transducer Temperature High S40 (Status; Diagnosis) 6.1.42. Transducer Temperature Low S41 (Status; Diagnosis) 6.1.43. Transducer Temperature Calibration S42 (Status; Diagnosis) Page 102 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 109: Appendix J: Hazardous Area Installations

    FM/CSA: see on page 107 Intrinsically Safe wiring drawing (FM/CSA) for reference drawing number 23650617) Under the entity evaluation concept, SITRANS Probe LU has the following characteristics: = 24 V DC (max.) (input voltage) U (input current) I = 250 mA DC (max.) = 1.2 W...
  • Page 110: Fm/Csa

    For complete details and instructions regarding the FISCO Concept, see page Intrinsically Safe wiring drawing (FM/CSA) on page 107 for drawing number 23650617, also available from the product page of our website: www.siemens.com/ processautomation. The FISCO Concept allows interconnection of intrinsically safe apparatus to associated apparatus not specifically examined in such combination.
  • Page 111: Eu Equivalency

    • The safe area is unspecified except that it must not be supplied from nor contain, under normal or abnormal conditions, a source of potential with respect to earth in excess of 250 V rms or 250 V DC. 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 105...
  • Page 112: Device Nameplate

    Oxley Creek WWTP Water Reclamation Doc Id: VM11 (Probe LU Manual) Vendor Manual Active Date: 15/12/2006 Device Nameplate Page 106 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 113: Intrinsically Safe Wiring Drawing (Fm/Csa)

    ULTRASONICS 18 / APRIL / 2005 R. CLYSDALE SITRANS Probe LU E. DeSIMONE PROFIBUS PA S. NGUYEN CONNECTION DRAWING PETERBOROUGH FOR INTERNAL USE ONLY 23650617 2365061700 1 : 1 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 107...
  • Page 114 ULTRASONICS 18 / APRIL / 2005 R. CLYSDALE SITRANS Probe LU E. DeSIMONE PROFIBUS PA S. NGUYEN CONNECTION DRAWING PETERBOROUGH FOR INTERNAL USE ONLY 23650617 2365061700 1 : 1 Page 108 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 115 ULTRASONICS 18 / APRIL / 2005 R. CLYSDALE SITRANS Probe LU E. DeSIMONE PROFIBUS PA S. NGUYEN CONNECTION DRAWING PETERBOROUGH FOR INTERNAL USE ONLY 23650617 2365061700 1 : 1 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 109...
  • Page 116 ULTRASONICS 18 / APRIL / 2005 R. CLYSDALE SITRANS Probe LU E. DeSIMONE PROFIBUS PA S. NGUYEN CONNECTION DRAWING PETERBOROUGH FOR INTERNAL USE ONLY 23650617 2365061700 1 : 1 Page 110 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 117: Non-Incendive (Fm Class I, Div. 2) Wiring Drawing

    29 / SEPT / 2004 R. CLYSDALE SITRANS Probe LU S. MILLIGAN CLASS I, Div. 2 S. NGUYEN CONNECTION DRAWING PETERBOROUGH FOR INTERNAL USE ONLY 23650583 2365058300 1 : 1 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 111...
  • Page 118: Instructions Specific To Hazardous Area Installations

    (Reference European ATEX Directive 94/9/EC, Annex II, 1/0/6) The following instructions apply to the SITRANS Probe LU covered by certificate number SIRA 03ATEX2142X: For use and assembly, refer to the main instructions. The equipment is certified for use as Category 1G equipment.
  • Page 119 The equipment marking contains at least the information on the product nameplate, shown on page 67. 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 113...
  • Page 120: Appendix K: Softw Are Revision History

    • Corrects a defect in the Volume Breakpoint 1.03 1.03.01 09/21/2005 table, where the table was not restored after a power failure. • • • • • • • Page 114 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 121: Glossary

    7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 115...
  • Page 122 The unit is a Henry. secondary echoes that appear as double, triple, or quadruple echoes in the distance from the target echo. Page 116 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 123 SITRANS Probe LU with Step 7, the Probe LU has a virtual “rack” to hold data distance between a transmitter and a target.
  • Page 124 Oxley Creek WWTP Water Reclamation Doc Id: VM11 (Probe LU Manual) Vendor Manual Active Date: 15/12/2006 Notes Page 118 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 125: Index

    (DD) overview diagnosis reply specifications diagnostics hysteresis dimensions setting distance 1 (SV2) specifications distance 2 (SV3) 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 119...
  • Page 126 (PV) setting becomes process variable memory LTB output menu structure volume output charts principles of operation menu timeout process temperature specifications process value scale setting Page 120 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 127 PROGRAM mode RUN mode secondary value LTB output secondary value 1 (SV1) level secondary value 2 secondary value 2 (SV2) distance 1 secondary value 3 (SV3) distance 2 7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 121...
  • Page 128 Oxley Creek WWTP Water Reclamation Doc Id: VM11 (Probe LU Manual) Vendor Manual Active Date: 15/12/2006 Page 122 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02...
  • Page 129 Oxley Creek WWTP Water Reclamation Doc Id: VM11 (Probe LU Manual) Vendor Manual Active Date: 15/12/2006...
  • Page 130 Doc Id: VM11 (Probe LU Manual) Vendor Manual Active Date: 15/12/2006 www.siemens.com/processautomation Siemens Milltronics Process Instruments Inc. Siemens Milltronics Process Instruments Inc. 2005 1954Technology Drive, P .O. Box 4225 Subject to change without prior notice Peterborough, ON, Canada K9J 7B1 *7ml19985JB02* Rev.

Table of Contents