Short-Circuit Protection: Contactor + 3Rr2 Monitoring Relay, Type Of Coordination 1 And 2 - Siemens SIRIUS Configuration Manual

Load feeders
Hide thumbs Also See for SIRIUS:
Table of Contents

Advertisement

Fused selection tables up to 690 V

5.5 Short-circuit protection: Contactor + 3RR2 monitoring relay, type of coordination 1 and 2

5.5
Short-circuit protection: Contactor + 3RR2 monitoring relay, type of
coordination 1 and 2
Short-circuit protection with fuses for motor feeders with 3RR2, contactor mounting, and stand-alone
assembly
Fuse links according to IEC 60947 and UL 508
Short-circuit protection up to 690 V / 100 kA, type of coordination 1 and 2
Table 5- 11
Fuse links for monitoring relay and contactor size S00 and S0
Monitorin
Overload
g relay
relay
Setting
range
MLFB
A
Size S00
3RR2.41
1,6 ... 16
Size S0
3RR2.42
4 ... 40
Take account of the operating voltage
1)
Assignment and short-circuit protective devices acc. to DIN EN 60947-4-1
2)
NH type 3NA, DIAZED type 5SB, NEOZED type 5SE, operating class gG
3)
RK1, RK5, J, CC
4)
82
Contactor
MLFB
kW
Stand-alone
assembly
3RT2015
35
3RT2016
35
3RT2017
50
3RT2018
50
Stand-alone
assembly
3RT2024
5,5
3RT2025
7,5
3RT2026
11,0
3RT2027
15,0
3RT2028
18,5
Fuse links
Acc. to IEC 60947
3)
Type of coordination
2)
1
2
50
50
35
20
35
20
50
25
50
25
125
80
63
25
63
25
100
35
125
50
125
50
Configuration Manual, 04/2010, A8E56203880102-02
1)
Acc. to UL 508
4)
(600 V)
Standard short-
High short-circuit
circuit rating
rating
60
100
100
Configuring SIRIUS Innovations
60

Advertisement