Siemens SIRIUS Configuration Manual page 56

Load feeders
Hide thumbs Also See for SIRIUS:
Table of Contents

Advertisement

Selection tables 500 V AC
4.2 Motor starter protector + contactor + thermal overload relay
Standard three-phase
motor 4-pole at
400 V AC
1)
Standard
Motor
output P
current I
kW
A
18,5
28
18,5
28
Short-circuit breaking capacity I
22
33
3)
22
33
3)
Order numbers for basic versions with screw terminals and spring-loaded terminals also possible.
Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data
1)
of the protected motor.
Rated control supply voltage 230 V AC, 50 Hz, other control voltages possible.
2)
Discrete mounting only, without a link module.
3)
56
Motor starter
Contactor
protector Starter
protection
Order No.
Order No.
3RV2321-4NC10
3RT2027-1AP00
3RV2321-4EC10
3RT2027-1AP00
= 36 kA
q
3RV2321-4PC10
3RT1035-1AP00
3RV2321-4PC10
3RT1035-1AP00
Size
2)
S0/S0/S0
S0/S0/S0
S0/S2/S0
S0/S2/S2
Configuration Manual, 04/2010, A8E56203880102-02
Thermal overload
Setting range
relay
Overload
release
Overload relay
Order No.
A
3RU2126-4NB0
23 ... 28
3RU2126-4EB0
27 ... 32
3RU2126-4PB0
30 ... 36
3RU1136-4FB0
28 ... 40
Configuring SIRIUS Innovations

Advertisement

Table of Contents
loading

Table of Contents