5.2 Short-circuit protection: Contactor + 3RU2 thermal overload relay, type of coordination 1 and 2
Overload relay thermal
MLFB
Setting range
Size S0
3RU2126-1CB0
1,8 ... 2,5
3RU2126-1DB0
2,2 -3,2
3RU2126-1EB0
2,8 ... 4,0
3RU2126-1FB0
3,5 ... 5,0
3RU2126-1GB0
4,5 ... 6,3
3RU2126-1HB0
5,5 ... 8,0
3RU2126-1JB0
7,0 ... 10
3RU2126-1KB0
9,0 ... 12,5
3RU2126-4AB0
11 ... 16
3RU2126-4BB0
14 ... 20
3RU2126-4CB0
17 ... 22
3RU2126-4DB0
20 ... 25
3RU2126-4NB0
23 ... 28
3RU2126-4EB0
27 ... 32
3RU2126-4PB0
30 ... 36
3RU2126-4FB0
34 ... 40
Please take account of the operating voltage
1)
Assignment and short-circuit protective devices acc. to DIN EN 60947-4-1
2)
Configuring SIRIUS Innovations
Configuration Manual, 04/2010, A8E56203880102-02
Contactor
MLFB
P [kW]
3RT2024-1..
5,5
3RT2024-1..
5,5
3RT2024-1..
5,5
3RT2024-1..
5,5
3RT2024-1..
5,5
3RT2024-1..
5,5
3RT2024-1..
5,5
3RT2024-1..
5,5
3RT2025-1..
7,5
3RT2026-1..
11
3RT2026-1..
11
3RT2026-1..
11
3RT2027-1..
15
3RT2027-1..
15
3RT2028-1..
18,5
3RT2028-1..
18,5
Fused selection tables up to 690 V
Fuse links
1)
Type of coordination
Type of coordination
1
2
2)
63
63
63
63
63
63
63
63
63
100
100
100
125
125
125
125
2)
10
10
16
20
20
25
25
25
25
35
35
35
50
50
50
50
73