Siemens SIRIUS Configuration Manual page 52

Load feeders
Hide thumbs Also See for SIRIUS:
Table of Contents

Advertisement

Selection tables 500 V AC
4.1 Motor starter protector + contactor
Standard three-phase motor
4-pole at 500 V AC
1)
Standard output P
Motor current I
kW
A
11
17,6
15
23
18,5
28
18,5
28
Short-circuit breaking capacity I
22
33
3)
Order numbers for basic versions with screw terminals and spring-loaded terminals also possible.
Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data
1)
of the protected motor.
Rated control supply voltage 230 V AC, 50 Hz, other possible.
2)
Discrete mounting only, without a link module.
3)
52
Setting range
Overload release
Motor starter protector
A
17 ... 22
20 ... 25
23 ... 28
27 ... 32
= 36 kA
q
30 ... 36
Motor starter
Contactor
protector Motor
protection
Order No.
Order No.
3RV2021-4CA10
3RT2026-1AP00
3RV2021-4DA10
3RT2027-1AP00
3RV2021-4NA10
3RT2027-1AP00
3RV2021-4EA10
3RT2027-1AP00
3RV2021-4PA10
3RT1035-1AP00
Configuration Manual, 04/2010, A8E56203880102-02
Size
2)
S0/S0
S0/S0
S0/S0
S0/S0
S0/S2
Configuring SIRIUS Innovations