Conductivity
of medium
For detection of empty sensor the min. conductivity must always be >50 μS/cm and the
max. length of the electrode cable when remote mounted is 50 meters (164 ft). Special
cable must be used!
For 19" Ex applications with safety barriers special cable cannot be used and the empty
pipe function can therefore not be used. For these applications 25 meters (82 ft) of cable
can be used in order to obtain 0.2% and 50 meters (164 ft) to obtain 0.4%.
For remote MID installations the max. cable length is 3 meters (9.8 ft). For other CT
application standard requirements are applicable.
8.4

Liner selection

Table 8- 13
Liner
EPDM
Ebonite
PTFE
PFA
Linatex
Soft rubber
SITRANS F M MAG 3100 sensor
Operating Instructions, 09/2012, A5E03005599-02
Special cable
[µS/cm]
50
40
30
20
10
5
50
100
200
150 300 600
900
Cable length
WARNING
300
400
500
[m]
1200
1500
[ft]
Applications
Drinking Water, Low abrasive media, Food & Beverage
Drinking Water, Wastewater, Fine low abrasive media
Drinking Water, Wastewater, Chemicals, Food & Beverage,
Pulp & Paper
Drinking Water, Wastewater, Chemicals, Food & Beverage,
Pulp & Paper
Abrasive media
Drinking Water, Wastewater, Abrasive media, Chemicals
Technical data
8.4 Liner selection
57