Installation Guidelines - Siemens SIRIUS Configuration Manual

Load feeders
Hide thumbs Also See for SIRIUS:
Table of Contents

Advertisement

Installation guidelines

The table below provides an overview of the installation guidelines for fuseless load feeders
(sizes S00 and S0).
Table 6- 1
Installation guidelines – fuseless load feeders (sizes S00 and S0)
Combination
Motor starter protector and
contactor
3RA21 direct starter, screw terminal, DIN rail or wall
S00
S0
3RA21 direct starter, screw terminal, busbar
S00
S0
3RA22 reversing starter, screw terminal, DIN rail or wall
S00
S0
Configuring SIRIUS Innovations
Configuration Manual, 04/2010, A8E56203880102-02
Output
Distance between feeders
Permissible installation: h = horizontal, v = vertical
A
mm
h, v
≤ 14
0 h, v
14 ... 16
10 h
0 h, v
≤ 29
0 h, v
29 ... 32
10 h
0 h, v
≤ 14
0 h
10 h
10 v
14 ... 16
10 h
10 v
≤ 29
0 h
10 h
10 v
29 ... 32
10 h
10 v
≤ 14
0 h, v
14 ... 16
10 h
0 h, v
≤ 29
0 h, v
29 ... 32
10 h
0 h, v
Max. ambient temperature
Vibration and shock
°C
60
Unlimited
60
40
60
DIN rail adapter required
60
40
40
Vibration and shock kit 8US1998-1CA10 required
60
40
60
40
40
Vibration and shock kit 8US1998-1CA10 required
60
40
60
40
60
DIN rail adapter required
60
40
60
DIN rail adapter required
(already included with 3RA22)
60
40
1
6
91