Siemens SIRIUS Configuration Manual page 81

Load feeders
Hide thumbs Also See for SIRIUS:
Table of Contents

Advertisement

Fuse links according to IEC 60947 and UL 508
Short-circuit protection up to 690 V / 100 kA, type of coordination 1 and 2
Table 5- 10
Fuse links for overload relay and contactor size S00 and S0
Overload
Overload
relay
relay
Setting range
MLFB
A
Size S00
3UF7100-
0,3 ... 3,0
1AA00-0/
3RB2906-
2BG1
3UF7101-
2,4 ... 25
1AA00-0/
3RB2906-
2DG1
Size S0
3UF7101-
2,4 ... 25
1AA00-0/
3RB2906-
2DG1
3UF7102-
10 ... 100
1AA00-0/
3RB2906-
2JG1
Take account of the operating voltage
1)
Assignment and short-circuit protective devices acc. to DIN EN 60947-4-1
2)
NH type 3NA, DIAZED type 5SB, NEOZED type 5SE, operating class gG
3)
RK1, RK5, J, CC
4)
Configuring SIRIUS Innovations
Configuration Manual, 04/2010, A8E56203880102-02
5.4 Short-circuit protection: Contactor + 3UF7 + 3RB22 / 23 solid-state overload relay
Contactor
MLFB
kW
Stand-alone assembly
3RT2015
3,0
3RT2016
4,0
3RT2017
5,5
3RT2018
7,5
3RT2015
3,0
3RT2016
4,0
3RT2017
5,5
3RT2018
7,5
Stand-alone assembly
3RT2024
5,5
3RT2025
7,5
3RT2026
11,0
3RT2027
15,0
3RT2028
18,5
Stand-alone assembly
3RT2024
5,5
3RT2025
7,5
3RT2026
11,0
3RT2027
15,0
3RT2028
18,5
Fused selection tables up to 690 V
Fuse links
Acc. to IEC 60947
3)
Type of coordination
2)
1
2
50
25
35
20
35
20
50
25
50
25
35
20
35
20
50
25
50
25
125
50
63
25
63
25
100
35
125
50
125
50
315
315
63
25
63
25
100
35
125
50
125
50
1)
Acc. to UL 508
4)
(600 V)
Standard short-
High short-
circuit rating
circuit rating
10
10
100
100
400
400
81

Advertisement

Table of Contents
loading