Troubleshooting

Fault codes

Displayed
System characteris-
fault code
tics
10
Regulates as if the
outside temperature
was 0 °C
18
Regulates as if the
outside temperature
was 0 °C
20
Regulates without
flow temperature
sensor (low loss
header)
28
Regulates without
flow temperature
sensor (low loss
header)
30
Burner blocked
38
Burner blocked
40
Mixer closes
44
Mixer closes
48
Mixer closes
4C
Mixer closes
50
No DHW heating
104
Cause
Measures
Short circuit, out-
Check the outside tem-
side temperature
perature sensor (see
sensor
page 116).
Lead break, out-
Check the outside tem-
side temperature
perature sensor (see
sensor
page 116).
Short circuit, sys-
Check the low loss header
tem flow tempera-
sensor (see page 117)
ture sensor
Lead break, sys-
Check the low loss header
tem flow tempera-
sensor (see page 117)
ture sensor
Short circuit, boiler
Check the boiler water
water temperature
temperature sensor (see
sensor
page 117)
Lead break, boiler
Check the boiler water
water temperature
temperature sensor (see
sensor
page 117)
Short circuit, flow
Check flow temperature
temperature sen-
sensor
sor, heating circuit
2 (with mixer)
Short circuit, flow
Check flow temperature
temperature sen-
sensor
sor, heating circuit
3 (with mixer)
Lead break, flow
Check flow temperature
temperature sen-
sensor
sor, heating circuit
2 (with mixer)
Lead break, flow
Check flow temperature
temperature sen-
sensor
sor, heating circuit
3 (with mixer)
Short circuit, cylin-
Check sensors (see
der temperature
page 117)
sensor