Viessmann FB2B Installation And Service Instructions Manual page 85

4.8 to 26 kw gas condensing/solar storage combi boiler natural gas and lpg version gas council no.: 47-819-18 19 kw 47-819-19 26 kw
Table of Contents

Advertisement

Select boiler
(cont.)
Coding in the delivered condition
21:0
No service interval (hours
run) selected
23:0
No time interval for
burner service
24:0
No "Service" display
28:0
No burner interval igni-
tion
2E:0
Never adjust
2F:0
Venting program/fill pro-
gram disabled
30:0
Never adjust
38:0
Status burner control unit:
Operational (no fault)
Possible change
21:1
The number of hours run
to
before the burner should
21:100
be serviced is adjustable
from 100 to 10 000 h
One adjusting step ≙
100 h
23:1
Interval adjustable from 1
to
to 24 months
23:24
24:1
"Service" display (the
address is automatically
set and must be manually
reset after a service has
been carried out)
28:1
Time interval adjustable
to
from 1 h to 24 h. The burner
28:24
is force-started once every
30 s (only when operating
with LPG).
2F:1
Venting program enabled
2F:2
Fill program enabled
Status burner control unit:
38:≠0
Fault
Code 2
85