Fault codes
(cont.)
Displayed
System characteris-
fault code
tics
EC
Burner in a fault
state
Ed
Burner in a fault
state
EE
Burner in a fault
state
EF
Burner in a fault
state
Cause
Measures
Parameter fault
Press reset button R
during calibration
or
Replace boiler coding
card and press reset but-
ton R.
Internal fault
Replace the control unit.
Flame signal is not
Check gas supply (gas
present or too
pressure and gas flow lim-
weak at burner
iter);
start
check gas train.
Check the ionisation elec-
trode and connecting
cable.
Checking ignition:
■ Connecting leads to
■ Distance to ignition
Check condensate drain.
Press reset button R.
The flame is lost
Check gas supply (gas
immediately after it
pressure and gas flow lim-
has built (during
iter).
the safety time).
Check flue gas/ventilation
air system for flue gas
recirculation.
Check ionisation elec-
trode (replace if required):
■ Distance to burner
■ Contamination of elec-
Press reset button R.
Troubleshooting
ignition module and
ignition electrode
electrode and contami-
nation (see page 40).
gauze assembly (see
page 40)
trode