Viessmann FB2B Installation And Service Instructions Manual page 112

4.8 to 26 kw gas condensing/solar storage combi boiler natural gas and lpg version gas council no.: 47-819-18 19 kw 47-819-19 26 kw
Table of Contents

Advertisement

Troubleshooting
Fault codes
(cont.)
Displayed
System characteris-
fault code
tics
F0
Burner blocked
F1
Burner in a fault
state
F2
Burner in a fault
state
F3
Burner in a fault
state
F7
Burner blocked
F8
Burner in a fault
state
F9
Burner in a fault
state
FA
Burner in a fault
state
FC
Burner in a fault
state
112
Cause
Measures
Internal fault
Replace the control unit.
Flue gas tempera-
Check the heating system
ture limiter has
fill level. Vent the system.
responded.
Press reset button R after
the flue system has
cooled down.
The temperature
Check the heating system
limiter has respon-
fill level. Check the circu-
ded.
lation pump. Vent the sys-
tem. Check the tempera-
ture limiter and connect-
ing cables.
Press reset button R.
Flame signal is
Check the ionisation elec-
already present at
trode and connecting
burner start.
cable.
Press reset button R.
Short circuit or lead
Check the water pressure
break, water pres-
sensor and the connect-
sure sensor
ing cable.
The fuel valve
Check the gas train.
closes too late.
Check both control paths.
Press reset button R.
Fan speed too low
Check the fan, the fan
during burner start
connecting cables and
power supply; check the
fan control.
Press reset button R.
Fan not at stand-
Check the fan, fan con-
still
necting cables and fan
control.
Press reset button R.
Gas train faulty or
Check the gas train.
faulty modulation
Check the flue gas sys-
valve control or flue
tem.
gas path blocked
Press reset button R.