Code 2
General
(cont.)
Coding in the delivered condition
9C:20
Monitoring LON subscrib-
ers.
If a subscriber fails to
respond, the values
specified inside the con-
trol unit will be used after
20 min. Only then will a
fault message be issued.
(only for weather-com-
pensated control units)
9F:8
Differential temperature
8 K; only in conjunction
with the mixer circuit (only
for weather-compensa-
ted control units)
Select boiler
Coding
Coding in the delivered condition
04:1
Minimum burner pause
subject to the boiler load
(specified by boiler cod-
ing card)
06:...
Maximum limit of the
boiler water temperature,
specified in °C by the
boiler coding card
0d:0
Do not adjust
0E:0
Do not adjust
13:1
Do not adjust
14:1
Do not adjust
15:1
Do not adjust
84
Possible change
9C:0
No monitoring
9C:5
The time is adjustable from
to
5 to 60 min
9C:60
9F:0
Differential temperature
to
adjustable from 0 to 40 K
9F:40
Possible change
04:0
Minimum burner pause set
permanently (specified by
boiler coding card)
Adjust for systems with low
loss header.
06:20
Maximum limit of the boiler
to
water temperature within
06:127
the ranges specified by the
boiler