Troubleshooting
Fault codes
(cont.)
Displayed
System characteris-
fault code
tics
E8
Burner in a fault
state
EA
Burner in a fault
state
Eb
Burner in a fault
state
110
Cause
Measures
The ionisation cur-
Check gas supply (gas
rent lies outside the
pressure and gas flow lim-
permissible range
iter), gas train and con-
necting lead.
Check allocation of gas
type (see page 32).
Check ionisation elec-
trode:
■ Distance to burner
■ Contamination of elec-
Press reset button R.
Ionisation current
Check flue system; rem-
outside the permis-
edy flue gas recirculation
sible range during
if required.
calibration (devia-
In open flue mode, pre-
tion from previous
vent very dusty conditions
level too great)
for the combustion air.
Press reset button R.
Following several unsuc-
cessful reset attempts,
replace boiler coding card
and press reset button R.
Repeated flame
Check gap between ioni-
loss during calibra-
sation electrode and
tion
burner gauze assembly
(see page 40).
Check allocation of gas
type (see page 32).
Check flue system; rem-
edy flue gas recirculation
if required.
Press reset button R.
gauze assembly (see
page 40)
trode