Viessmann FB2B Installation And Service Instructions Manual page 109

4.8 to 26 kw gas condensing/solar storage combi boiler natural gas and lpg version gas council no.: 47-819-18 19 kw 47-819-19 26 kw
Table of Contents

Advertisement

Fault codes
(cont.)
Displayed
System characteris-
fault code
tics
dF
Control mode without
room influence
E0
Control mode
E1
Burner in a fault
state
E3
Burner in a fault
state
E4
Burner blocked
E5
Burner blocked
E6
Burner blocked
E7
Burner in a fault
state
Cause
Measures
Lead break, room
Check room temperature
temperature sen-
sensor for heating circuit 3
sor, heating circuit
and remote control set-
3 (with mixer)
tings (see page 143)
Fault external LON
Check connections and
subscriber
LON subscribers
Ionisation current
Check gap between ioni-
too high during cal-
sation electrode and
ibration
burner gauze assembly
(see page 40).
In open flue mode, pre-
vent very dusty conditions
for the combustion air.
Press reset button R.
Heat transfer too
Ensure adequate heat
low during calibra-
transfer.
tion.
Press reset button R.
Temperature lim-
iter caused shut-
down.
Fault, supply volt-
Replace the control unit.
age 24 V
Fault, flame ampli-
Replace the control unit.
fier
System pressure
Top up with water.
too low
Ionisation current
Check ionisation elec-
too low during cali-
trode:
bration
■ Distance to burner
■ Contamination of elec-
■ Connecting lead and
Check flue system; rem-
edy flue gas recirculation
if required.
Press reset button R.
Troubleshooting
gauze assembly (see
page 40)
trode
plug-in connections
109