Code 1
Heating circuit 1, heating circuit 2, heating...
Coding in the delivered condition
Flow temperature minimum limit
C5:20
Electronic minimum flow
temperature limit 20 °C
Flow temperature maximum limit
C6:74
Electronic maximum flow
temperature limit set to
74 °C
Heating program - changeover
d5:0
External heating program
changeover changes to
"Constant operation with
reduced room tempera-
ture" or "Standby mode".
Ext. heating program changeover to heating circuit
d8:0
No heating program
changeover via extension
EA1
Screed function
F1:0
Screed function disa-
bled.
74
(cont.)
Possible change
C5:1
Minimum limit adjustable
to
from 1 to 127 °C (limited by
C5:127
boiler-specific parameters)
C6:10
Maximum limit adjustable
to
from 10 to 127 °C (limited
C6:127
by boiler-specific parame-
ters)
d5:1
The external heating pro-
gram changeover changes
to "Constant operation with
standard room tempera-
ture" (independent of cod-
ing address 3A, 3b and
3C)
d8:1
Heating program change-
over via input DE1 at exten-
sion EA1
d8:2
Heating program change-
over via input DE2 at exten-
sion EA1
d8:3
Heating program change-
over via input DE3 at exten-
sion EA1
F1:1
Screed drying function
to
adjustable in accordance
F1:6
with 6 optional tempera-
ture/time profiles (see
page 137)
F1:15
Constant flow temperature
20 °C