Viessmann FB2B Installation And Service Instructions Manual page 82

4.8 to 26 kw gas condensing/solar storage combi boiler natural gas and lpg version gas council no.: 47-819-18 19 kw 47-819-19 26 kw
Table of Contents

Advertisement

Code 2
General
(cont.)
Coding in the delivered condition
79:1
With LON communication
module: Control unit is
fault manager (only for
weather-compensated
control units)
7b:1
With LON communication
module: The control unit
transmits the time (only
for weather-compensa-
ted control units)
7F:1
Detached house (only for
weather-compensated
control units)
80:6
A fault message is dis-
played, providing a fault
is active for at least 30 s
81:1
Automatic summer/win-
ter time changeover
82:0
Operation with natural
gas
86:0
Do not adjust
87:0
Do not adjust
88:0
Temperature displayed in
°C (Celsius)
8A:175
Do not adjust
8F:0
All control elements
active
82
Possible change
79:0
Control unit is not fault
manager
7b:0
Does not transmit time
7F:0
Apartment building
Separate adjustment of
holiday program and time
program for DHW heating,
as option
80:0
Immediate fault message
80:2
Minimum fault duration
to
until fault message occurs,
80:199
adjustable from 10 s to
995 s; 1 step ≙ 5 s
81:0
Manual summer/winter
time changeover
81:2
Use of the radio clock
receiver (automatic recog-
nition)
81:3
With LON communication
module: The control unit
receives the time
82:1
Operation with LPG (only
adjustable if coding
address 11:9 has been
set)
88:1
Temperature displayed in
°F (Fahrenheit)
8F:1
All control elements locked
out
8F:2
Only standard settings can
be controlled