Power System Data 2; Functional Description; Setting Notes - Siemens SIPROTEC 4 Manual

Overcurrent time protection
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Functions
2.1 General

Power System Data 2

2.1.6
2.1.6.1

Functional Description

The general protection data (P.System Data 2) include settings associated with all functions rather than a
specific protection or monitoring function. In contrast to the P.System Data 1 as discussed before, they
can be changed with the setting group.
Applications
When the primary reference voltage and the primary reference current of the protected object are set, the
device is able to calculate and output the operational measured value percentage.
For purposes of fault location, a maximum of three different line sections can be considered.
2.1.6.2

Setting Notes

Definition of Nominal Rated Values
At addresses 1101 FullScaleVolt. and 1102 FullScaleCurr., the primary reference voltage (phaseto-
phase) and reference current (phase) of the protected equipment is entered. If these reference sizes match
the primary nominal values of the VTs and CTs, they correspond to the settings in address 202 and 204
(Section
2.1.3.2 Setting
Ground Impedance Ratios (only for Fault Location)
The adjustment of the ground impedance ratio is only important for the utilization of the line fault location
function. This is done by entering the resistance ratio RE/RL and the reactance ratio XE/XL.
The values under addresses 1103 and 1104 apply if only one line section is available and to all faults that
occur outside the defined line sections.
If several line sections are set, the following shall apply:
for line section 1, addresses 6001 and 6002
for line section 1, addresses 6011 and 6012
for line section 1, addresses 6021 and 6022.
Resistance ratio RE/RL and reactance ratio XE/XL are calculated formally and do not correspond to the real
and imaginary components of Z
line data using the following formulas:
[formelfehlerorter-260602-kn, 1, en_US]
Where
R
0
X
0
R
1
X
1
This data can be used for the entire line or line section, or as distance-related values, since the quotients are
independent of the distance.
Calculation example:
20 kV free line 120 mm
R
/s = 0.88 Ω/km (1.42 Ω/mile)
0
X
/s = 1.26 Ω/km (2.03 Ω/mile)
0
R
/s = 0.24 Ω/km (0.39 Ω/mile)
1
50
Notes). They are generally used to show values referenced to full scale.
/Z
. No complex calculation is required! The ratios can be obtained from the
E
L
– Zero sequence resistance of the line
– Zero sequence reactance of the line
– Positive sequence resistance of the line
– Positive sequence reactance of the line
2
with the following data:
Zero sequence resistance
Zero sequence reactance
Positive sequence resistance
SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec 7sj80Siprotec 4 7saj8

Table of Contents