Settings - Siemens SIPROTEC 4 Manual

Overcurrent time protection
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Voltage Difference
The parameters 6150 dV SYNCHK V2>V1 and 6151 dV SYNCHK V2<V1 can be set to adjust the permissible
voltage differences asymmetrically. The availability of two parameters enables an asymmetrical release to be
set.

Settings

2.20.7
Addresses which have an appended "A" can only be changed with DIGSI, under "Additional Settings".
Addr.
Parameter
6101
Synchronizing
6102
SyncCB
6103
Vmin
6104
Vmax
6105
V<
6106
V>
6107
SYNC V1<V2>
6108
SYNC V1>V2<
6109
SYNC V1<V2<
6110A
Direct CO
6111A
TSUP VOLTAGE
6112
T-SYN. DURATION
6113A
25 Synchron
6121
Balancing V1/V2
6122A
ANGLE ADJUSTM.
6123
CONNECTIONof V2
6125
VT Vn2, primary
6150
dV SYNCHK V2>V1
6151
dV SYNCHK V2<V1
6152
df SYNCHK f2>f1
6153
df SYNCHK f2<f1
6154
dα SYNCHK α2>α1
6155
dα SYNCHK α2<α1
SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
Setting Options
ON
OFF
(Setting options depend on
configuration)
20 .. 125 V
20 .. 140 V
1 .. 60 V
20 .. 140 V
YES
NO
YES
NO
YES
NO
YES
NO
0.00 .. 60.00 sec
0.01 .. 1200.00 sec; ∞
YES
NO
0.50 .. 2.00
0 .. 360 °
A-B
B-C
C-A
0.10 .. 800.00 kV
0.5 .. 50.0 V
0.5 .. 50.0 V
0.01 .. 2.00 Hz
0.01 .. 2.00 Hz
2 .. 80 °
2 .. 80 °
Default Setting
Comments
OFF
Synchronizing Function
none
Synchronizable circuit breaker
90 V
Minimum voltage limit: Vmin
110 V
Maximum voltage limit: Vmax
5 V
Threshold V1, V2 without voltage
80 V
Threshold V1, V2 with voltage
NO
ON-Command at V1< and V2>
NO
ON-Command at V1> and V2<
NO
ON-Command at V1< and V2<
NO
Direct ON-Command
0.10 sec
Supervision time of V1>;V2> or
V1<;V2<
30.00 sec
Maximum duration of Synchroni-
zation
YES
Switching at synchronous condi-
tion
1.00
Balancing factor V1/V2
0 °
Angle adjustment (transformer)
A-B
Connection of V2
20.00 kV
VT nominal voltage V2, primary
5.0 V
Maximum voltage difference
V2>V1
5.0 V
Maximum voltage difference
V2<V1
0.10 Hz
Maximum frequency difference
f2>f1
0.10 Hz
Maximum frequency difference
f2<f1
10 °
Maximum angle difference
alpha2>alpha1
10 °
Maximum angle difference
alpha2<alpha1
Functions
2.20 Synchrocheck
271

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec 7sj80Siprotec 4 7saj8

Table of Contents