Functional Description - Siemens SIPROTEC 4 Manual

Overcurrent time protection
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

i
, i
, i
, i
, i
and v
A
B
C
N
Ns
(voltages depending on connection) are sampled at intervals of 1.0 ms (at 50 Hz) and stored in a revolving
buffer (20 samples per cycle). In the event of a fault, the data are recorded for a set period of time, but not for
more than 5 seconds. A maximum of 8 faults can be recorded in this buffer. The fault record memory is auto-
matically updated with every new fault, so no acknowledgment for previously recorded faults is required. In
addition to protection pickup, the recording of the fault data can also be started via a binary input or via the
serial interface.
2.1.4.1

Functional Description

The data of a fault event can be read out via the device interface and evaluated with the help of the SIGRA 4
graphic analysis software. SIGRA 4 graphically represents the data recorded during the fault event and also
calculates additional information from the measured values. Currents and voltages can be presented either as
primary or as secondary values. Signals are additionally recorded as binary tracks (marks), e.g. "pickup", "trip".
If port B of the device has been configured correspondingly, the fault record data can be imported by a central
controller via this interface and evaluated. Currents and voltages are prepared for a graphic representation.
Signals are additionally recorded as binary tracks (marks), e.g. "pickup", "trip".
The retrieval of the fault data by the central controller takes place automatically either after each protection
pickup or after a tipping.
If device parameter 651 ParEN100(LC)blk is set to ON, you can also read out fault records via port A (see
Section
2.1.2.2 Setting
Depending on the selected type of connection of the voltage transformers (address 213 VT Connect. 3ph),
the following measured values are recorded in the fault record:
Voltage connection
Van, Vbn, Vcn
v
yes
AB
v
yes
BC
v
yes
CA
v
yes
A
v
yes
B
v
yes
C
v
v
yes
en
v
SYN
v
x
NOTE
i
i
The signals used for the binary tracks can be allocated in DIGSI.
NOTE
i
i
If one of the current transformer connection types A,G2,C,G; G->B or A,G2,C,G; G2->B has been
selected via parameter 251 CT Connect., the ground current Ι
former is indicated under track Ι
cated under track Ι
SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
, v
, v
, v
, v
, v
, v
, v
A
B
C
A2
B3
C1
N
Notes).
Vab, Vbc,
Vab, Vbc
VGnd
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
. The ground current detected by the fourth current transformer is indi-
N
.
Ns
, v
, v
X
ph-n
SYN
Vab, Vbc, Vx
Vab, Vbc, VSyn
yes
yes
yes
yes
measured with the second current trans-
N2
Functions
2.1 General
Vph-g, VSyn
yes
yes
yes
yes
yes
yes
47

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec 7sj80Siprotec 4 7saj8

Table of Contents