Settings Eptr, Tnp; Information List - Siemens SIPROTEC 4 Manual

Overcurrent time protection
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Addr.
Parameter
3160
α1 red.dir.area
3161
α2 red.dir.area

Settings EPTR, TNP

2.12.7
Addresses which have an appended "A" can only be changed with DIGSI, under "Additional Settings".
The table indicates region-specific default settings. Column C (configuration) indicates the corresponding
secondary nominal current of the current transformer.
Addr.
Parameter
3501
EPTR
3502
Trans. Neutral
3503
Pickup current
3504
Pickup current
3505
EPTR I Tmax
3506
TNP I Tmax
3507
EPTR I Tmin
3508
TNP I Tmin
3509
EPTR I Tknee
3510
TNP I Tknee
3511
T knee
3512
T min
3513
T max
3514
T Function

Information List

2.12.8
No.
Information
1201
>BLOCK 64
1202
>BLOCK 50Ns-2
1203
>BLOCK 50Ns-1
1204
>BLOCK 51Ns
1207
>BLK 50Ns/67Ns
1211
50Ns/67Ns OFF
1212
50Ns/67Ns ACT
1215
64 Pickup
SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
C
Setting Options
1 .. 15 °
1 .. 15 °
C
Setting Options
OFF
ON
OFF
ON
1A
0.001 .. 1.400 A
5A
0.005 .. 7.000 A
0.05 .. 4.00 A
1A
0.001 .. 1.400 A
5A
0.005 .. 7.000 A
0.05 .. 4.00 A
1A
0.003 .. 4.000 A
5A
0.015 .. 20.000 A
0.05 .. 20.00 A
1A
0.003 .. 1.400 A
5A
0.015 .. 7.000 A
0.05 .. 17.00 A
0.20 .. 100.00 sec
0.10 .. 30.00 sec
0.50 .. 300.00 sec
-0.50 .. 30.00 sec
Type of
Comments
Informa-
tion
SP
>BLOCK 64
SP
>BLOCK 50Ns-2
SP
>BLOCK 50Ns-1
SP
>BLOCK 51Ns
SP
>BLOCK 50Ns/67Ns
OUT
50Ns/67Ns is OFF
OUT
50Ns/67Ns is ACTIVE
OUT
64 displacement voltage pick up
2.12 Ground Fault Protection 64, 67N(s), 50N(s), 51N(s)
Default Setting
Comments
2 °
Alpha1 (reduction direc-
tional area)
2 °
Alpha2 (reduction direc-
tional area)
Default Setting
Comments
OFF
EPTR
OFF
Transformer Neutral
protection(TNP)
0.008 A
Pickup current
0.040 A
0.12 A
Pickup current
0.008 A
Current at Maximum Time
Delay
0.040 A
0.12 A
Current at Maximum Time
Delay
3.333 A
Current at Minimum Time
Delay
16.665 A
1.00 A
Current at Minimum Time
Delay
0.100 A
Current at Knee Point
0.500 A
0.20 A
Current at Knee Point
26.70 sec
Time Delay at Knee Point
0.80 sec
Minimum Time Delay
139.90 sec
Maximum Time Delay
0.00 sec
Delay time T of the whole
function
Functions
195