Electrical Tests - Siemens SIPROTEC 4 Manual

Overcurrent time protection
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Technical Data
4.1 General Device Data
DNP3.0 /MODBUS FO
FO connector type
Terminal
Transmission speed
Optical wavelength
Laser Class 1 according to EN 60825-1/-2
Permissible optical signal attenuation
Bridgeable distance
Ethernet electrical (EN 100) for DIGSI, IEC61850, DNP3 TCP, Modbus TCP, IEC60870-5-104, PROFINET,
SICAM I/O Unit 7XV5673
Terminal
Test voltage (with regard to the socket)
(PELV)
Transmission speed
Bridgeable distance
Ethernet optical (EN 100) for DIGSI, IEC61850, DNP3 TCP, Modbus TCP, IEC60870-5-104, PROFINET,
SICAM I/O Unit 7XV5673
Terminal
Transmission speed
Optical wavelength
Bridgeable distance

Electrical Tests

4.1.5
Regulations
Standards:
Insulation Test
Standards:
Voltage test (routine test) of all circuits except
auxiliary voltage, binary inputs and communication
ports
Voltage test (routine test) of auxiliary voltage and
binary inputs
Voltage test (routine test) of isolated communica-
tion ports only (A and B)
Impulse voltage test (type test) of all process
circuits (except for communication ports) against
the internal electronics
358
ST connector transmitter/receiver
Back case bottom, mounting location "B"
up to 19,200 Bd
λ = 820 nm
When using glass fiber 50 μm/125 μm or glass fiber 62.5/125 μm
max. 8 dB, with glass fiber 62.5/125 μm
max. 1.5 km
Back case bottom, mounting location "B",
2 x RJ45 socket
100BaseT according to IEEE802.3
500 V; 50 Hz
100 MBit/s
20 m
Back case bottom, mounting location "B",
Duplex-LC, 100BaseF according to IEEE802.3
100 MBit/s
1300 nm
max. 2 km (1.24 mi)
IEC 60255
IEEE Std C37.90, see individual functions
VDE 0435
for more standards see also individual functions
IEC 60255-27 and IEC 60870-2-1
2.5 kV, 50 Hz
DC 3.5 kV
500 V, 50 Hz
6 kV (peak value);
1.2 µs/50 µs; 0.5 J;
3 positive and 3 negative impulses at intervals of 1 s
SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017