Information List - Siemens SIPROTEC 4 Manual

Overcurrent time protection
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Addr.
Parameter
2101
67Nc-2 PICKUP
2102
67Nc-2 DELAY
2103
67Nc-1 PICKUP
2104
67Nc-1 DELAY
2105
67Nc-TOC PICKUP
2106
67Nc-TOC T-DIAL
2107
67Nc-TOC T-DIAL
2108
67Nc-3 PICKUP
2109
67Nc-3 DELAY
2.4.4

Information List

No.
Information
1730
>BLOCK CLP
1731
>BLK CLP stpTim
1732
>ACTIVATE CLP
1994
CLP OFF
1995
CLP BLOCKED
1996
CLP running
1997
Dyn set. ACTIVE
SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
C
Setting Options
1A
0.05 .. 35.00 A; ∞
5A
0.25 .. 175.00 A; ∞
0.00 .. 60.00 sec; ∞
1A
0.05 .. 35.00 A; ∞
5A
0.25 .. 175.00 A; ∞
0.00 .. 60.00 sec; ∞
1A
0.05 .. 4.00 A
5A
0.25 .. 20.00 A
0.05 .. 3.20 sec; ∞
0.50 .. 15.00 ; ∞
0.25 .. 35.00 A; ∞
0.00 .. 60.00 sec; ∞
Type of
Comments
Informa-
tion
SP
>BLOCK Cold-Load-Pickup
SP
>BLOCK Cold-Load-Pickup stop timer
SP
>ACTIVATE Cold-Load-Pickup
OUT
Cold-Load-Pickup switched OFF
OUT
Cold-Load-Pickup is BLOCKED
OUT
Cold-Load-Pickup is RUNNING
OUT
Dynamic settings are ACTIVE
2.4 Dynamic Cold Load Pickup
Default Setting
Comments
7.00 A
67Nc-2 Pickup
35.00 A
0.00 sec
67Nc-2 Time Delay
1.50 A
67Nc-1 Pickup
7.50 A
0.30 sec
67Nc-1 Time Delay
1.00 A
67Nc-TOC Pickup
5.00 A
0.50 sec
67Nc-TOC Time Dial
5.00
67Nc-TOC Time Dial
∞ A
67Nc-3 Pickup
0.00 sec
67Nc-3 Time Delay