Address 664 IP adr[0] (Sec) to 667 IP adr[3]
(Sec)
Address 668 Client activ
Address 669 Daylight Set
Address 670 Offset TZ/min
Address 671 Offset DayT/min
Address 672 W2S month to 675 W2S hour
Address 676 S2W month to 679 S2W hour
Access authorization for port A
At address 651 ParEN100(LC)blk you can parameterize a read access option via the EN100 module at port
A. If the parameter is set to ON, you can read out the device parameters using DIGSI or fetch fault records.
IEC 61850 GOOSE Function
At address 700 GOOSE-Stop you can set the GOOSE function of the IEC 61850 protocol to active or not. If
GOOSE-Stop is set to YES, you can release the GOOSE function again via a binary input during operation.

Settings

2.1.2.3
Addr.
Parameter
610
FltDisp.LED/LCD
611
Spont. FltDisp.
640
Start image DD
651
ParEN100(LC)blk
660
IP adr[0](Prim)
661
IP adr[1](Prim)
662
IP adr[2](Prim)
663
IP adr[3](Prim)
664
IP adr[0] (Sec)
665
IP adr[1] (Sec)
666
IP adr[2] (Sec)
667
IP adr[3] (Sec)
668
Client activ
669
Daylight Set
670
Offset TZ/min
671
Offset DayT/min
SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
Setting Options
Target on PU
Target on TRIP
YES
NO
image 1
image 2
image 3
image 4
image 5
image 6
OFF
ON
0 .. 255
0 .. 255
0 .. 255
0 .. 255
0 .. 255
0 .. 255
0 .. 255
0 .. 255
OFF
ON
OFF
ON
-1440 .. 1440 min
-1440 .. 1440 min
IP-Addresses 0 to 3, NTP secondary
client for primary and secondary addresses switched
on or off.
daylight saving time switched on or off.
offset for the time zone in minutes
offset for daylight saving time in minutes
month, week (of the month), day of the week, hour
of switching to daylight saving time
month, week (of the month), day of the week, hour
of switching to winter time
Default Setting
Comments
Target on PU
Fault Display on LED / LCD
NO
Spontaneous display of flt.annun-
ciations
image 1
Start image Default Display
OFF
DIGSI-config. over EN100 (LC)
blocked
0
IP address [0] (NTP-Primary)
0
IP address [1] (NTP-Primary)
0
IP address [2] (NTP-Primary)
0
IP address [3] (NTP-Primary)
0
IP address [0] (NTP-Sekundary)
0
IP address [1] (NTP-Sekundary)
0
IP address [2] (NTP-Sekundary)
0
IP address [3] (NTP-Sekundary)
OFF
Client activ
OFF
Daylight Set
60 min
Offset for time zone in minutes
60 min
Offset for daylight in minutes