EN100-Module

2.1.7
2.1.7.1

Functional Description

The Ethernet EN100-Modul enables integration of the 7SJ80 in 100-Mbit communication networks in control
and automation systems with the protocols according to IEC 61850 standard. This standard permits uniform
communication of the devices without gateways and protocol converters. Even when installed in heteroge-
neous environments, SIPROTEC 4 relays therefore provide for open and interoperable operation. Parallel to the
process control integration of the device, this interface can also be used for communication with DIGSI and for
inter-relay communication via GOOSE.
2.1.7.2

Setting Notes

Interface Selection
No special settings are required for operating the Ethernet system interface module (IEC 1850, Ethernet
EN100-Modul). If the ordered version of the device is equipped with such a module, it is automatically allo-
cated to the interface available for it, namely Port B.
IEC 61850 GOOSE Function
The GOOSE function can be disabled via a device parameter. For more information, please refer to Section
2.1.2.2 Setting
2.1.7.3

Information List

No.
Information
009.0100 Failure Modul
009.0101 Fail Ch1
009.0102 Fail Ch2
SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
Notes.
Type of
Informa-
tion
IntSP
IntSP
IntSP
Comments
Failure EN100 Modul
Failure EN100 Link Channel 1 (Ch1)
Failure EN100 Link Channel 2 (Ch2)