Settings; Information List - Siemens SIPROTEC 4 Manual

Overcurrent time protection
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Settings

2.5.5
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secon-
dary nominal current of the current transformer.
Addr.
Parameter
2701
50 1Ph
2703
50 1Ph-2 PICKUP
2704
50 1Ph-2 DELAY
2706
50 1Ph-1 PICKUP
2707
50 1Ph-1 DELAY

Information List

2.5.6
No.
Information
5951
>BLK 50 1Ph
5952
>BLK 50 1Ph-1
5953
>BLK 50 1Ph-2
5961
50 1Ph OFF
5962
50 1Ph BLOCKED
5963
50 1Ph ACTIVE
5966
50 1Ph-1 BLK
5967
50 1Ph-2 BLK
5971
50 1Ph Pickup
5972
50 1Ph TRIP
5974
50 1Ph-1 PU
5975
50 1Ph-1 TRIP
5977
50 1Ph-2 PU
5979
50 1Ph-2 TRIP
5980
50 1Ph I:
SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
C
Setting Options
OFF
ON
1A
0.001 .. 1.600 A; ∞
5A
0.005 .. 8.000 A; ∞
0.00 .. 60.00 sec; ∞
1A
0.001 .. 1.600 A; ∞
5A
0.005 .. 8.000 A; ∞
0.00 .. 60.00 sec; ∞
Type of
Comments
Informa-
tion
SP
>BLOCK 50 1Ph
SP
>BLOCK 50 1Ph-1
SP
>BLOCK 50 1Ph-2
OUT
50 1Ph is OFF
OUT
50 1Ph is BLOCKED
OUT
50 1Ph is ACTIVE
OUT
50 1Ph-1 is BLOCKED
OUT
50 1Ph-2 is BLOCKED
OUT
50 1Ph picked up
OUT
50 1Ph TRIP
OUT
50 1Ph-1 picked up
OUT
50 1Ph-1 TRIP
OUT
50 1Ph-2 picked up
OUT
50 1Ph-2 TRIP
VI
50 1Ph: I at pick up
2.5 Single-Phase Overcurrent Protection
Default Setting
Comments
OFF
50 1Ph
0.300 A
50 1Ph-2 Pickup
1.500 A
0.10 sec
50 1Ph-2 Time Delay
0.100 A
50 1Ph-1 Pickup
0.500 A
0.50 sec
50 1Ph-1 Time Delay
Functions
121