Information List; Measurement - Siemens SIPROTEC 4 Manual

Overcurrent time protection
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Functions
2.23 Auxiliary Functions
relationship of make-break operations and tripping current. The two vertices of this characteristic in a double
logarithmic scale are decisive for the setting of addresses 260 to 263:
Point P1 is determined by the number of permitted make-break operations (parameter 261 OP.CYCLES AT
Ir) for rated operational current Ιr (parameter 260 Ir-52)
Point P2 is determined by the maximum number of make-break operations (parameter 263 OP.CYCLES Isc)
for rated fault tripping current Ιsc (parameter 262 Isc-52).
For the procedure to operate correctly, the time response of the circuit breaker must be specified in parame-
ters 266T 52 BREAKTIME and 267T 52 OPENING.
2
t-Procedure
Ι
The Ι
t-procedure is activated via configuration parameter 172 52 B.WEAR MONIT. The square fault current
2
integrals are referred to the squared device nominal current. For purposes of determining the arc time, the
device must be informed of the CB tripping time T 52 BREAKTIME as well as the CB opening time T 52
OPENING of the circuit breaker. For recognition of the last zero crossing (arc deletion) of the currents after
tripping, the "Current-zero" Criterion is required.
2.23.2.4

Information List

No.
Information
-
#of TRIPs=
409
>BLOCK Op Count
1020
Op.Hours=
1021
Σ Ia =
1022
Σ Ib =
1023
Σ Ic =
2896
79 #Close1./3p=
2898
79 #Close2./3p=
16001
ΣI^x A=
16002
ΣI^x B=
16003
ΣI^x C=
16006
Resid.Endu. A=
16007
Resid.Endu. B=
16008
Resid.Endu. C=
16011
mechan.TRIP A=
16012
mechan.TRIP B=
16013
mechan.TRIP C=
16014
ΣI^2t A=
16015
ΣI^2t B=
16016
ΣI^2t C=

Measurement

2.23.3
A series of measured values and the values derived from them are constantly available for call up on site, or
for data transfer.
Applications
Information on the actual status of the system
Conversion of secondary values to primary values and percentages
288
Type of
Comments
Informa-
tion
PMV
Number of TRIPs=
SP
>BLOCK Op Counter
VI
Counter of operating hours
VI
Accumulation of interrupted current Ph A
VI
Accumulation of interrupted current Ph B
VI
Accumulation of interrupted current Ph C
VI
No. of 1st AR-cycle CLOSE commands,3pole
VI
No. of higher AR-cycle CLOSE commands,3p
VI
Sum Current Exponentiation Ph A to Ir^x
VI
Sum Current Exponentiation Ph B to Ir^x
VI
Sum Current Exponentiation Ph C to Ir^x
VI
Residual Endurance Phase A
VI
Residual Endurance Phase B
VI
Residual Endurance Phase C
VI
Number of mechanical Trips Phase A
VI
Number of mechanical Trips Phase B
VI
Number of mechanical Trips Phase C
VI
Sum Squared Current Integral Phase A
VI
Sum Squared Current Integral Phase B
VI
Sum Squared Current Integral Phase C
SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017