Characteristics - Siemens SIPROTEC 4 Manual

Overcurrent time protection
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Introduction

1.3 Characteristics

1.3
Characteristics
General Characteristics
Powerful 32-bit microprocessor system
Complete digital processing and control of measured values, from the sampling of the analog input quan-
tities to the initiation of outputs, for example, tripping or closing circuit breakers or other switchgear
devices
Total electrical separation between the internal processing stages of the device and the external trans-
former, control, and DC supply circuits of the system because of the design of the binary inputs, outputs,
and the DC or AC converters
Complete set of functions necessary for the proper protection of lines, feeders, motors, and busbars
Easy device operation through an integrated operator panel or by means of a connected personal
computer running DIGSI
Continuous calculation and display of measured and metered values on the front of the device
Storage of min./max. measured values (slave pointer function) and storage of long-term mean values
Recording of event and fault data for the last 8 system faults (fault in a network) with real-time informa-
tion as well as instantaneous values for fault recording for a maximum time range of 20 s
Constant monitoring of the measured quantities, as well as continuous self-diagnostics covering the
hardware and software
Communication with SCADA or substation controller equipment via serial interfaces through the choice
of data cable, modem, or optical fibers
Battery-buffered clock which can be synchronized via a synchronization signal at the binary input or via a
protocol
Switching statistics: Counting the number of trip commands initiated by the device, logging the currents
of the last switch-off operation initiated by the device, and accumulating the eliminated short-circuit
currents of each breaker pole
Operating hours counter: Counting the operating hours of the protected object under load
Commissioning aids such as connection and direction check, status indication of all binary inputs and
outputs, easy testing of port B, and influencing of information at port B during test operation.
Time Overcurrent Protection 50, 51, 50N, 51N
Three definite time overcurrent protective elements and one inverse time overcurrent protective element
for phase current and ground current Ι
Two-phase operation of the overcurrent protection (Ι
For inverse-time overcurrent protection, selection from various characteristics of different standards
possible
Blocking is possible, e.g. for reverse interlocking with any element
Instantaneous tripping by any element is possible when switching onto a fault
In-rush restraint with second harmonic current quantities.
Ground Fault Protection 50N, 51N
Three definite time overcurrent protective elements and one inverse time overcurrent protective element
applicable for grounded or high-resistance grounded systems
For inverse-time overcurrent protection, selection from various characteristics of different standards
24
or summation current 3Ι
N
0
, Ι
) is possible
A
C
SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec 7sj80Siprotec 4 7saj8

Table of Contents