8.3

SETUP [02]

Setting the device parameters.
Factory-set parameter values are printed in bold in the table.
 
 
01
 
DIGITAL IN
01
BEHAVIOR DI
02
POLARITY DI
02
 
DIGITAL OUT
01
BEHAVIOR DO
02
POLARITY DO
03
DO POS LIMIT
03
DIRECTION
SIPART PS100
Operating Instructions, 06/2023, A5E50188938-AF
Meaning
 
Digital input (DI)
MENU
Menu for setting the digital input (DI)
 
Behavior at digital input
NONE
Sets the digital input to inactive.
HOLD
Sets the digital input to keep the valve position.
BUTTN
Sets the digital input to button lock.
MSG
Enables the digital output.
GO CL
Moves to the valve position when digital input is activated, as set in
parameter "CLOSE LIMIT" [05].
GO OL
Moves to the valve position when digital input is activated, as set in
parameter "OPEN LIMIT" [07].
 
Polarity of the digital input
HIGH
Normally Open: Normally open contact
LOW
Normally Close: Normally closed contact
 
Digital output (DO)
MENU
Menu for setting the digital output (DO)
 
Behavior at digital output
NONE
Sets the digital output to inactive.
ERR
Enables the digital output in case of control deviation or device error.
ERR M
Enables the digital output in case of manual operation, control devi‐
ation or device error.
POS
Enables the digital output when the value of the "DO POS LIMIT" [03]
parameter is reached.
 
Polarity of the digital output
HIGH
Normally Open: Normally open contact
LOW
Normally Close: Normally closed contact
0.0 ... 10.0 ...
Specifies the value as a percentage at which the digital output is en‐
100.0
abled. Values < 50 correspond to a low limit value. Values ≥ 50 corre‐
spond to a high limit value.
AUTO
Sets the operating direction of the valve defined during initialization.
INVRT
Inverts the operating direction of the valve defined during initializa‐
tion.
Parameter assignment and addressing
8.3 SETUP [02]
45