Specifications - Omron SYSMAC C500 Installation Manual

Hide thumbs Also See for SYSMAC C500:
Table of Contents

Advertisement

Appendix B
Power Supply Model
Supply Voltage
Operating Voltage Range
Power Consumption
Output Capacity
24 VDC Output*
Insulation Resistance
Dielectric Strength**
Noise Immunity
Vibration Resistance
Shock
Ambient Temperature
Humidity
Atmosphere
Grounding
Structure
Weight
*This output is not provided on Model PS223-E.
**When performing the dielectric strength test or the insulation resistance test be sure to disconnect the LG terminals from
the GR (ground) terminals to protect the program and internal parts from damage.

Specifications

3G2A5-PS221-E/222-E/223-E
100 to 120/200 to 240 VAC
(selectable) 50/60 Hz
85 to 132/170 to 264 VAC
150 VA max.
PS221: 7 A 5 VDC
PS223: 120 A 5 VDC
PS222: 7 A 5 VDC
0.8 A 24 VDC 10%
5 M
min. (at 500 VDC) between AC terminals
1,500 VAC 50/60 Hz for 1 minute
(between AC and GR terminals)
leakage current 10 m A max.
1,000 Vp-p, pulse width: 1
Mechanical durability: 10 to 25 Hz, 2 mm double amplitude, in X, Y, and Z
directions, for 2 hours each
Electrical durability: 16.7 Hz, 1 mm double amplitude, in X, Y, and Z directions,
for 10 minutes each
2
98 m/s
in downward direction, 3 times
Operating: 0 to 55 C
Storage: –20 to 65 C
35% to 85% RH (without condensation)
Must be free from corrosive gasses
Less than 100
Panel-mounted
8 kilograms max.
3G2A5-PS212-E/213-E
24 VDC
20.4 to 26.4 VDC
55 W max.
PS213: 9 A 5 VDC
PS212: 7 A 5 VDC
Not provided
500 VAC 50/60 Hz for 1 minute
(between DC and GR terminals)
leakage current 1 mA max.
µ
s, rise time: 1 ns
57