Specifications

1-3

Specifications

1-3-1

General Specifications

1-3-2

Specifications

Item
Product name
Model numbers
Non-duplex Inner Boards
Duplex Inner Boards
Applicable CPU
CS1W-LCB01
Units
CS1W-LCB05
Process-control CPU Unit
Unit classification
Data exchange
Words in Auxiliary Area in
method with CPU
CPU Unit
Unit
Allocated Words to Inner
Board in CIO Area of CPU
Unit
Allocated Words to Inner
Board in DM Area of CPU Unit
User allocations in I/O mem-
ory
EM Area (bank number) allo-
cations (for SCADA software)
Setting
Indicators
Front panel interface
Super capacitor backup data
Super capacitor backup time
Data stored in flash memory
Backup from RAM to flash memory
These specifications conform to the general specifications of the SYSMAC
CS-series.
Loop Control Board, Process-control CPU Unit, Loop-control CPU
Unit
Loop Control Board: CS1W-LCB01 and CS1W-LCB05
Loop-control CPU Unit: CJ1G-CPU@@P
Process-control CPU Unit: CS1D-CPU@@P
CS1G/H-CPU@@H
CS1D-CPU@@S (supported for Loop Control Board version 1.5 or
later only)
CS1D-CPU Unit with built-in Duplex Loop Controller
CS-series Inner Board
Loop Controller → CPU Unit:
Operation status, PV error input ON, MV error input ON, occur-
rence of execution error, function block database error, cold start
ready for hot start command, flash memory backup in progress,
function blocks changed, etc.
CPU Unit → Loop Controller:
Hot/cold start command at power ON (Not supported for CS1D-
CPU@@P.)
Not used
Not used
User memory tables used to allocate function block ITEM data for
user-specified memory in the CPU Unit (CIO, Work, HR, DM, or
EM Area (bank 0, but also banks 1 to 12 for Ver. 3.0 or later)).
HMI function used allocate function block ITEM data for Control,
Operation, External Controller, and System Common blocks in the
specified bank of the EM Area in the CPU Unit.
The real PV in calibration mode can be allocated (Ver. 3.0 or later).
None
Loop-control CPU Units: 2 LEDs (RUN and ready)
Other Controllers:
3 LEDs: RUN, ready, and communications port send/receive
RS-232C port x 1 (Used for connection to ES100X Controller.)
(Not supported by Loop-control CPU Units and Process-control
CPU Units.)
All function block data (including Step Ladder Program com-
mands), stored error log data
CS Series (CS1W-LCB01/05 or CS1D-CPU@@P): 24 hours at
25°C (life shortened by use at higher temperatures)
CJ Series (CJ1G-CPU@@P): 5 min at 25°C (Backed up by the Bat-
tery in the CPU Unit.)
Function block data
Executed from CX-Process Tool (as required).
Section 1-3
Specification
51