Omron SYSMAC C500 Installation Manual page 23

Hide thumbs Also See for SYSMAC C500:
Table of Contents

Advertisement

Description of All Components
3G2A5-PS222-E
Mounting screw
Do not loosen this screw.
Fuse holder
Contains a MF61NR fuse
(3 A, 250 V, 6.35-dia. x32)
POWER indicator
Lights when power is supplied.
Terminals for
external connections
Mounting screw
Do not loosen this screw.
3G2A5-PS212-E
Mounting screw
Do not loosen this screw.
Fuse holder
Contains a MF61NR fuse
(3 A, 250 V, 6.35-dia. x32)
POWER indicator
Lights when power is supplied.
Terminals for
external connections
Mounting screw
Do not loosen this screw.
AC input
Voltage selector
Short: 100 to 120 V
Open: 200 to 240 V
LG
GR
+
0.8 A, 24 VDC output
-
+
24 VDC input
-
LG
GR
Section 2
Connect a 100 to 120 VAC or 200 to
240 VAC power source
Short these terminals to select 100 to
120 VAC. Open them to select 200 to
240 VAC.
Ground this terminal at a resistance
of less than 100
to improve noise
immunity or prevent electric shock.
Ground this terminal at a resistance
of less than 100
to prevent electric
shock.
Use these terminals to supply power
to DC Input Units. Use a separate
Power Supply if the I/O Unit operate
on more than 0.8 A. If a current higher
than 0.8 A is output, the PC stops.
These terminals are used to supply
external DC Input Units. If the Unit re-
quires more than 0.8 A a separate
supply must be used. The PC shuts off
automatically if a current of more than
0.8 A is drawn from the supply.
Connect a 24-VDC power source (2.3
A min.)
Ground this terminal at a resistance
of less than 100
to improve noise
immunity or prevent electric shock.
Ground this terminal at a resistance
of less than 100
to prevent electric
shock.
15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents