Timing; Dc Output Unit 3G2A5-Od211 - Omron SYSMAC C500 Installation Manual

Hide thumbs Also See for SYSMAC C500:
Table of Contents

Advertisement

Specifications

Timing

DC Output Unit
3G2A5-OD211
24 k
1 W
24 k
1 W
Display no.
8
68
These pulses are input as data to bits 0 through 7 of word n.
Data 0 through 7
4 ms
STB 0
STB 1
STB 2
STB 3
STB 4
STB 5
STB 6
STB 7
By using the OD211 DC Output Unit, a large number of bits can be controlled
through only 16 points. Just like the ID211 DC Input Unit, different combina-
tions of points can access bits and words to control different outputs. Using
this type of Unit can simplify wiring when many bits must be controlled. Up to
64 bits can be accessed.
Because the output data is positive logic, the terminal output goes high when
the output data is logical 1. The strobe output is negative logic, so when a
signal is output, the corresponding terminal goes low. Use positive logic out-
put devices for the load of this Unit. The strobe output is cyclically and auto-
matically output.
7
6
5
32 ms
6 5 4 3
4
3
2
Appendix B
0
DATA 0
1
DATA 1
2
DATA 2
3
DATA 3
4
DATA 4
5
DATA 5
6
DATA 6
7
DATA 7
8
CON (0 V)
9
STB 0
10
STB 1
11
STB 2
12
STB 3
13
STB 4
14
STB 5
15
STB 6
16
STB 7
24 VDC
17
CON (0 V)
18
24 VDC
19
NC
7
1
11
1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents