Cpu Power Supply - Omron SYSMAC C500 Installation Manual

Hide thumbs Also See for SYSMAC C500:
Table of Contents

Advertisement

Description of All Components
2-2

CPU Power Supply

3G2A5-PS221-E
Mounting screw
Do not loosen this screw.
Fuse holder
Contains a MF61NR fuse
(3 A, 250 V, 6.35-dia. x32)
POWER indicator
Lights when power is supplied.
Terminals for
external connections
Mounting screw
Do not loosen this screw.
12
The CPU Power Supply is mounted to the rightmost slot of the CPU Rack.
Three models of Power Supplies are available: 100 to 120 VAC, 200 to 240
VAC, and 24 VDC. The following table summarizes the output capacity of the
three models and the current available for I/O Units mounted on the CPU
Rack.
Model
Supply Voltage
3G2A5-PS221-E 100 to 120/
200 to 240 VAC
200 to 240 VAC
3G2A5-PS223-E
(selectable)
3G2A5-PS213-E 24 VDC
Note
Be sure to keep the total power consumed by all the Units mounted
on a Rack within the value stated in the table above. For example, do
not mount I/O Units with a total current consumption of 6 A to a Rack
supplied by a 7 A Power Supply. As shown in the table above, the
available current for I/O Units is only 5 A. For details concerning cur-
rent consumption, refer to Section 4 System Connections .
Voltage selector
Short: 100 to 120 V
Open: 200 to 240 V
+
+
0.8 A, 24 VDC output
Output
Available Current
Capacity
for I/O Units
7 A 5 VDC
5 A
12 A 5 VDC 10 A
9 A 5 VDC
5 A
AC input
Connect a 100 to 120 VAC or 200 to
240 VAC power source.
Short these terminals to select 100 to
120 VAC. Open them to select 200 to
240 VAC.
Ground this terminal at a resistance of
LG
less than 100
munity or prevent electric shock.
Ground this terminal at a resistance
of less than 100
GR
shock.
Use these terminals to supply power
to DC Input Units. Use a separate
Power Supply if the I/O Unit requires
more than 0.8 A. If a current higher
than 0.8 A is output, the PC stops.
These terminals are short-circuited as
START input
a factory-set condition. Remove the
short-circuit bracket to start or stop
the PC with an external signal. Nor-
mally, leave them short-circuited.
These terminals are turned ON dur-
RUN output
ing RUN operation.
Section 2
24 VDC Output
Terminal
Provided
Not provided
Not provided
to improve noise im-
to prevent electric