Specifications

Dummy I/O Unit

84
Selection Function Unit designation: input/output Point designation: 16/32/64
points
Internal Current
35 mA 5 VDC max.
Consumption
Power for External
30 mA 24 VDC 10% min.
Supply
Weight
450 grams max.
Terminal
Connections
Dimensions
A-shape
Note
Power is supplied to the Dummy I/O Unit from the 24 VDC output
terminal of the Power Supply, which is mounted on the same Rack
as the Dummy I/O Unit. Be sure to supply power to the Dummy I/O
Unit before supplying power to the CPU. If power is supplied to the
Dummy I/O Unit after power is supplied to the CPU, the Dummy I/O
Unit is assumed to have only 16 I/O points, and may result in an I/O
Verification Error or an I/O Setting Error.
3G2A5-DUM01
Short-circuit:
Open:
Point
Terminal
designation
connection
16 points
Open 3,4, and 5
32 points
Short 3 and 4.
Open 5.
64 points
Short 4 and 5.
Open 3.
Appendix B