Omron SYSMAC C500 Installation Manual page 78

Hide thumbs Also See for SYSMAC C500:
Table of Contents

Advertisement

Specifications
Max. Switching Capacity
Max. Surge Current
Min. Switching Capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Points
Internal Current Consumption
Fuse Capacity
Power for External Supply
Weight
Circuit Configuration
Terminal Connections
Dimensions
1.2 A 250 VAC, 50/60 Hz (4 A/common, 5 A/unit)
15 A for 100 ms pulse width, 30 A for 10 ms pulse width
100 mA at 10 VAC, 50 mA at 24 VAC
10 mA at 100 VAC, 10 mA at 240 VAC
1.5 mA (120 VAC, 60 Hz) max., 3.0 mA (240 VAC, 60 Hz) max.
1.5 VAC max. for 100 to 600 mA, 1.5 VAC for 50 to 100 mA,
5.0 VAC for 10 to 50 mA
1 ms max.
1/2 of load frequency + 1 ms max.
16 (8 points/common, 2 circuits)
450 mA at 5 VDC max.
5 A, 250 V; 6.35 mm dia. x 32 mm (two fuses)
600 grams max.
Inter-
nal
Circuit
250 VAC
max.
250 VAC
max.
A-shape
C500-OA226
OUT 00
47 Ω
47 Ω
to
0.022 µF
OUT 06
Fuse/fuse blowout
OUT 07
detection circuit
COM
OUT 08
47 Ω
47 Ω
to
0.022 µF
OUT 14
Fuse/fuse blowout
OUT 15
detection circuit
COM
0
0
L
1
1
L
2
2
L
3
3
L
4
4
L
~
5
5
L
6
6
L
7
7
L
COM
8
8
9
L
9
10
L
10
11
L
11
12
L
12
13
L
~
13
14
L
14
15
L
15
16
L
COM
17
NC
18
19
NC
Appendix B
73

Hide quick links:

Advertisement

Table of Contents
loading