OF = 0
OVERRIDE FUNCTION
OF = 0: The thermostat will control its own relays (Default)
OF = 1: The five thermostat relays are being controlled via a ModBus master
only. No thermostat buttons will function and all programming and
control information is suppressed. The word Override will flash
during this mode. The thermostat will automatically exit this mode if
no valid ModBus signals have been received for five minutes.
RS = 40
THERMOSTAT SENSOR RESPONSE TIME TO ROOM
TEMPERATURE CHANGES
Adjustable from RS = 10 (very fast) to RS = 90 (very slow). Default is RS = 40
TS = 0
FACTORy TeST MOde (See PAge 47)
TS = 0:
Factory test Mode OFF
TS = 1:
Display configuration code*
TS = 2:
Step cycle all relays in sequence, 1 2 3 4 5 etc
TS = 3:
Reset software to factory default. Press Fan button to initiate
* This table is available from the download section at www.robertshaw.com.