SH = OFF
STOP HeATiNg TeMPeRATuRe (COMMeRCiAL MOde)
Start/Stop Mode Only. (Sw6 = ON, Sw8 = OFF)
Heating temperature that will be maintained when running the STOP program
(Night Setback). Adjustable between 41 to 120ºF (5 to 49ºC) + OFF.
db = 1 (0.5) SiNgLe SeTPOiNT deAdbANd (See PAge 22)
Deadband between Heat and Cool setpoints when in single setpoint mode
(Sw8 = OFF).
Adjustable between 0 and 10 degrees in 1 degree steps for Fahrenheit.
Adjustable between 0 and 10 degrees in 0.5 degree steps for Celsius.
FO = 0
FAN OPTiONS - AdvANCed FAN FuNCTiONS
This function is only enabled when the selected fan mode is Fan ON.
FAN ON will be displayed in the LCD to confirm the mode.
FO = 0: Default Residential Mode. The fan will run continuously, 24 hours a
day seven days a week.
FO =1:
The fan will continue to run after the cooling stops to ensure
maximum fresh air ventilation and to aid in cooling. The fan will stop
after the heating stops. This is done to prevent cold drafts that may
occur on cold days when A/C system is heating.
28