TD = 0
TEMPERATURE DISPLAY
TD = 0: The thermostat will display both the room and set temperatures
TD = 1: The thermostat will display set temperature only
AH = 2
AFTER HOURS OVERRIDE TIMER
Start/Stop Mode: Commercial Thermostat Mode (Sw6 = ON, Sw8 = OFF)
After Hour Run Time Period: Adjustable range 0 (OFF) to 12 hours in 0.5 steps
Setback (1, 2, 3 ,4) Mode: Residential Programmable Mode (Sw6 = ON,
Sw8 = ON). Temporary program override period.
OFF = Override till next program change or 1 - 12 hours (fixed time override)
ST = OFF
START PROgRAM TeMPeRATuRe (COMMeRCiAL MOde)
Start/Stop Mode only (Sw6 = ON, Sw8 = OFF)
This sets the default temperature that will be used each time the Start
program begins, regardless of any adjustments the user may have made
previously. Adjustable between OFF and 59 to 95ºF (15 to 35ºC). If set to OFF,
the user setpoint will not be automatically reset to a default value each day.
SC = OFF
STOP COOLiNg TeMPeRATuRe (COMMeRCiAL MOde)
Start/Stop Mode Only. (Sw6 = ON, Sw8 = OFF)
Cooling temperature that will be maintained when running the STOP program
(Night Setback). Adjustable between 43 to 122ºF (6 to 50ºC) + OFF.
27