DT = 20
UPSTAGE DELAY TIME
Time in minutes before next stage of heating or cooling is to be called.
Delay only operates if the stage trip temperature has not yet been reached.
Adjustable between OFF, 5 to 90 minutes in five minute steps.
OS = 0
OPTiMized START/STOP (AdAPTive ReCOveRy)
(See PAge 48)
OS = 0: Optimized start/stop function OFF
OS = 1: Optimized start/stop function RUNNING
C2 = 0.0
CALIbRATION REMOTE SENSOR
Calibration Offset for the TT terminal temperature sensor
Adjustable range +/- 9°F degrees (4.5°C degrees).
CO = 45ºF (7ºC) COOLiNg OFF TeMPeRATuRe (See PAge 48)
Only operates if TT = OA and outside temperature sensor is fitted.
Outside air temperature below this value will force the cooling function OFF.
Adjustable between 41 to 122°F in steps of 1.0 degree.
Adjustable between 5 to 50°C in steps of 0.5 degree.
34