Table 1
Hardware Switch Settings (Full descriptions on following pages)
Switch
Sw1 – Fan Speeds
Sw2 – Equipment Type
Sw3 – Stages
Sw4 – Reversing Valve
If Sw 2= ON – Heat Pump
Sw4 – Fan Mode
If Sw 2= OFF – Heat/cool
Sw5 – Anti-Cycle Timer
Sw6 – Operation
Sw7 – Minimum Run
Sw8 – Program Type
If Sw 6 = ON – Programmable
Sw8 – Setpoints
If Sw 6 = OFF – Manual
Off
1 Speed Fan
(2 Heat / 2 Cool)
Heat / Cool
1 Stage
Energize in cool (O)
Fan Control by
Heater (HG)
Off
Manual Thermostat
2 Minutes
Commercial Program
Single Setpoint
11
On
3 Speed Fan
(1 Heat / 1 Cool)
Heat Pump
(O/B terminals)
2 Stages
Energize in heat (B)
Fan Control by
Thermostat (HE)
4 Minutes
Programmable
Thermostat
6 Minutes
Residential Program
Two Setpoints