Waterbox Removal And Installation; Discussion; Procedure - Trane CVHH Installation, Operation And Maintenance Manual

Water-cooled centravac chillers with tracer adaptiview control
Hide thumbs Also See for CVHH:
Table of Contents

Advertisement

Waterbox Removal and Installation

Im port ant : Only qualified technicians should perform
the installation and servicing of this
equipm ent.

Discussion

This section w ill discuss recom m ended lifting. Proper
lifting technique w ill vary based on m echanical room
layout.
It is the responsibility of the person(s) perform ing the
w ork to be properly trained in the safe practice of
rigging, lifting, securing, and fastening of the
waterbox.
It is the responsibility of the person(s) providing and
using the rigging and lifting devices to inspect these
devices to ensure they are free from defect and are
rated to m eet or exceed the published w eight of the
waterbox.
Always use rigging and lifting devices in accordance
w ith the applicable instructions for such device.

Procedure

WARNING
Heavy Objects!
Failure to properly lift waterbox could result in death or
serious injury. Each of the individual cables (chains or
slings) used to lift the waterbox must be capable of
supporting the entire weight of the waterbox. The
cables (chains or slings) must be rated for overhead
lifting applications w ith an acceptable working load
limit. Refer to
Table 24, p. 99
Review m echanical room lim itations and determ ine the
safest m ethod or m ethods of rigging and lifting the
waterboxes.
1. Determ ine the type and size of chiller being serviced.
Refer to Trane nam eplate located on chiller control
panel.
Im port ant : This literature contains rigging and lifting
inform ation only for Trane CTV chillers built
in La Crosse. For Trane CTV chillers built
outside the United States, refer to literature
provided by the applicable m anufacturing
location.
2. The rated lifting capacity of the lifting shackle m ust
m eet or exceed the published w eight of the waterbox.
Verify the waterbox w eight from the latest published
literature.
3. Ensure that the lift connection device has the correct
size for the waterbox lifting hole.
4. Properly connect the shackle to the
waterbox.Figure 54, p. 98
98
for waterbox weights.
5. Disconnect water pipes, if connected.
6. Rem ove waterbox bolts.
7. Lift the waterbox away from the shell.
Figure 54. Waterbox lifting—condenser and evaporator
lifting points
Lift ing
locat ion
LIFTING
LOCATION
Lift ing
locat ion
LIFTING
LOCATION
WARNING
Overhead Hazard!
Failure to follow instructions could result in death or
serious injuries. Never stand below or in close
proximity to heavy objects w hile they are suspended
from, or being lifted by, a lifting device in case the
object drops.
8. Store waterbox in a safe and secure location and
position.
N ot e: Do not leave waterbox suspended from lifting
device.
Lift ing
locat ion
LIFTING
LOCATION
Lift ing
locat ion
LIFTING
LOCATION
CVHH-SVX001A-EN

Hide quick links:

Advertisement

Table of Contents
loading