CVHH Annual Inspection List
Follow the annual maintenance instructions provided in the text of this manual, including but
not limited to:
Compressor M otor
M otor continuity.
M otor m eg test.
Check m otor term inals.
Inspect m otor term inal board.
Starter or AFD
Inspect starter contacts.
Check all connections per m anufacturer specifications.
Follow all m anufacturer recom m endations for starter or AFD m aintenance.
Inspect/clean/service the AFD cooling system (water- or air-cooled AFD).
Record all applicable starter or starter com ponent settings.
Oil System
Annual oil analysis (follow recom m endations).
Clean and lubricate oil system as required.
Electrical inspection.
Pum p m otor continuity check.
Run oil pum p and check differential oil pressure.
Condenser
Inspect for fouling and scaling in tubes.
Check operation of condenser water flow sensing device.
Factory recom m endation to eddy current test tubes every three years.
Evaporator
Inspect for fouling and scaling in tubes.
Check operation of evaporator water flow sensing device.
Factory recom m endation to eddy current test tubes every three years.
Control Circuits
Verify control param eters.
Test appropriate sensors for accuracy.
Ensure sensors are properly seated in w ells w ith therm opaste installed.
Check evaporator leaving water tem perature low tem perature cutout setpoint.
Condenser high pressure sw itch check-out.
Check adjustm ent and operation of the inlet guide vane actuator.
Leak Test Chiller
Check purge tim es and unit perform ance logs. If warranted, pressure leak test.
Review oil analysis. If required, subm it refrigerant sam ple for analysis.
Inspect unit for any signs of refrigerant or oil leakage.
Check unit for any loose bolts on flange, volutes, or casing.
Purge Unit
Review this m anual and follow m aintenance and/or inspection item s identified.
Review purge pum p out data.
Review overall operation of purge and service as necessary.
Exterior
Inlet guide vane linkage.
Clean and touch-up painted surfaces as needed.
Repair deteriorated, torn, or m issing insulation.