Trane CVHH Installation, Operation And Maintenance Manual page 47

Water-cooled centravac chillers with tracer adaptiview control
Hide thumbs Also See for CVHH:
Table of Contents

Advertisement

For AWG/M CM equivalents in m m
Table 12. Wire sizing reference
2
AW G/ M CM
m m
e qu iva le n t
22
0.32
21
0.35
20
0.5
18
0.75
17
1.0
16
1.5
14
2.5
12
4
10
6
8
10
6
16
4
25
2 or 1
35
1/ 0
50
2/ 0
70
2/ 0 or 3/ 0
95
4/ 0 or 250
120
300
150
350 or 400
185
450 or 500
240
Note: AWG = Am erican Wire Gauge
Im port ant : Custom ers are responsible for all field
w iring in com pliance w ith local, national,
and/or international codes.
WARNING
Hazardous Voltage w / Capacitors!
Failure to disconnect power and discharge capacitors
before servicing could result in death or serious injury.
Disconnect all electric power, including remote
disconnects and discharge all motor start/ run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. For variable frequency drives
or other energy storing components provided by Trane
or others, refer to the appropriate manufacturer's
literature for allowable waiting periods for discharge of
capacitors. Verify w ith an appropriate voltmeter that all
capacitors have discharged.
For additional information regarding the safe discharge of
capacitors, see PROD-SVB06* -EN
CVHH-SVX001A-EN
2
, refer to
Table
12:
WARNING
Personal Protective Equipment (PPE)
Required!
Failure to follow proper handling guidelines could
result in death or serious injury. Always wear
appropriate personal protective equipment in
accordance w ith applicable regulations and/ or
standards to guard against potential electrical shock
and flash hazards.
WARNING
Live Electrical Components!
Failure to follow all electrical safety precautions w hen
exposed to live electrical components could result in
death or serious injury. During installation, testing,
servicing and troubleshooting of this product, it may be
necessary to work w ith live electrical components.
Have a qualified licensed electrician or other individual
w ho has been properly trained in handling live
electrical components perform these tasks.
N ot e: Graphic labels (show n above) are used for CE
application only.
Im port ant :
Before servicing, disconnect all pow er sources and
allow at least 30 m inutes for capacitors to discharge.
All electrical enclosures—unit or rem ote—are IP2X.
Electrical Requirements
X39003892001A