Cvhh-Svx001A-En - Trane CVHH Installation, Operation And Maintenance Manual

Water-cooled centravac chillers with tracer adaptiview control
Hide thumbs Also See for CVHH:
Table of Contents

Advertisement

efector, " p.
23) are used to verify evaporator and
condenser water flow s.
If a custom er-supplied flow sensing device is used to
ensure adequate chiller protection, refer to the w iring
diagram s that shipped w ith the unit for specific electrical
connections.
Be sure to follow the m anufacturer 's recom m endations for
device selection and installation.
Water Flow Detection Controller and Sensor—ifm
efector
Figure 10. Installation of ifm efector flow detection
controller and sensor
n
pter (A) into pipe.
w probe (B) into adapter (A).
rail (F) into control cabinet.
trol monitor (C) onto DIN rail (F).
able (E) to low probe (B), (hand tighten only).
in combicon connectors (D) according to
gram.
outputs for low, wire-break, and/or
ure monitoring, according to wiring diagram.
w monitoring
L
monitoring
AC
Jumper
N
n series, use
ram at right.
toring
Jumper
monitoring
re monitoring
delay time
quid / gas
Output to
control cabinet
onitoring can
rated using
1, and 12.
1. M ount the 1/2-in. NPT adapter in a horizontal or
vertical section of pipe. The m axim um distance from
the control panel m ust not exceed 8.99 m eters (29.5 ft)
(see item labeled " 1" in
five pipe diam eters straight run of pipe upstream of the
sensor location, and three pipe diam eters straight run
of pipe dow nstream of the sensor location.
N ot e: In the case of a horizontal pipe, m ounting the
sensor in the side of the pipe is preferred. In the
case of a vertical pipe, m ounting the sensor in
a place w here the water flow s upwards is
preferred.

CVHH-SVX001A-EN

I f fact ory- provided,
locat ed in cont rol panel.
Components:
A. E40174 – 1/2" NPT adapter (for low probe)
B . SF6200 – Flow probe
C . SN0150 – Flow control monitor
D. E70231 – Combicon connectors (quantity 5)
4
E . E10965 – Micro DC cable, 10m length, PUR jacket
F. F53003 – Din rail, 40mm length
Figure 10, p.
23). Allow at least
2. Insert the flow probe through the 1/2-in. NPT adapter
as near the center of the pipe as possible (see item
labeled " 2" in
1/2-in. NPT adapter; then, tighten w ith a w rench an
additional 1-1/4 turns.
N ot e: When installed, the tip of the ifm efector sensor
probe m ust be at least 2.54 cm (1 in.) away from
any pipe wall. Placing the tip of the probe at the
center of the pipe is preferred.
3. Install the M icro DC Cable by inserting it through the
w ire openings on the back side of the control panel (see
item labeled " 3" in
supplied M icro DC Cable (9 m eters [25 feet] in length)
to the Flow Probe and hand-tighten the connector nut.
4. Plug the other end of the M icro DC Cable into the Flow
Control M onitor w ith the Com bicon connector (see
item labeled " 4" in
for cable w iring.
3
2
1
Installation: Water Piping
Figure 10, p.
23). Finger-tighten the
Figure 10, p.
23). Install the
Figure 10, p.
23). Refer to
Figure 11
23