General Specifications - Omron Sysmac NX-PD1000 User Manual

Nx-series machine automation controller system units
Hide thumbs Also See for Sysmac NX-PD1000:
Table of Contents

Advertisement

2 Specifications
2-1

General Specifications

This table shows the general specifications of all System Units.
Enclosure
Grounding methods
Operating
Ambient operating temperature
environ-
Ambient operating humidity
ment
Atmosphere
Ambient storage temperature
Altitude
Pollution degree
Noise immunity
Overvoltage category
EMC immunity level
Vibration resistance
Shock resistance
Insulation resistance
Dielectric strength
Applicable standards
*1. Varies with NX Unit Models. Refer to A-1 Data Sheet on page A-2 for the specifications of NX Units.
*2. Refer to the OMRON website (www.ia.omron.com) or ask your OMRON representative for the most recent
applicable standards for each model.
2 - 2
Item
Mounted in a panel
Ground of 100 Ω or less
0 to 55°C
10 to 95% RH (with no icing or condensation)
Must be free from corrosive gases.
−25 to 70°C (with no icing or condensation)
2,000 m max.
Pollution degree 2 or less: Conforms to JIS B 3502 and IEC 61131-2.
Conforms to IEC 61000-4-4, 2 kV (power supply line)
Category II: Conforms to JIS B 3502 and IEC 61131-2.
Zone B
Conforms to IEC 60068-2-6.
5 to 8.4 Hz with amplitude of 3.5 mm,
8.4 to 150 Hz, acceleration of 9.8 m/s
100 min each in X, Y, and Z directions (10 sweeps of 10 min each =
100 min total)
Conforms to IEC 60068-2-27, 147 m/s
directions
*1
*1
cULus: Listed (UL508), ANSI/ISA 12.12.01, EU: EN 61131-2, C-Tick,
*2
KC: KC Registration, NK, LR
Specification
2
2
, 3 times each in X, Y, and Z
NX-series System Units User's Manual (W523)