Omron Sysmac NX-PD1000 User Manual page 141

Nx-series machine automation controller system units
Hide thumbs Also See for Sysmac NX-PD1000:
Table of Contents

Advertisement

Installation orientation
and restrictions
Terminal connection dia-
gram
NX-series System Units User's Manual (W523)
Installation orientation:
• Connected to a CPU Unit
Possible in upright installation.
• Connected to a Communications Coupler Unit
Possible in 6 orientations.
Restrictions: As shown in the following.
• For upright installation
Output power (W)
12
10
8
6
4
2
0
0
10
Ambient operating temperature (°C)
• For any installation other than upright
Output power (W)
12
10
8
6
4
2
0
0
10
Ambient operating temperature (°C)
24 VDC Unit
power supply
Ground of 100 Ω
or less
For 10 W output, 40°C
20
30
40
45
50
55
For 10 W output, 40°C
20
30
40
45
50
55
Additional NX Unit
Power Supply Unit
NX-PD1000
A1
B1
UV
UV
UG
UG
*2
*2
NC
NC
A8
B8
Appendices
For 8.5 W output, 55°C
60
For 6.0 W output, 55°C
60
Through-wiring for unwired terminals
A
*1
A - 5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents